Auxiliary Contact Composition:
1 NO + 1 NC
Color:
dark grey
Mounting Support:
plate
[Icw] Rated Short-Time Withstand Current:
1.1 kA - 10 s || 0.64 kA - 30 s || 0.52 kA - 1 min || 0.4 kA - 3 min || 0.32 kA - 10 min
Average Impedance:
0.00018 Ohm
Associated Fuse Rating:
125 A aM at <= 440 V for motor || 125 A aM at <= 690 V for motor || 315 A gG at <= 690 V
Operating Time:
40...70 ms closing || 15...50 ms opening
Contactor Application:
power switching
Inrush Power In Va:
290-290 VA
Product Or Component Type:
contactor
Pole Contact Composition:
4 NO
Hold-In Power Consumption In Va:
10-10 VA
Depth:
193 mm
Device Short Name:
LC1G
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Compatibility Code:
LC1G
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1
[Uimp] Rated Impulse Withstand Voltage:
8 kV
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Sustainable Offer Status:
Green Premium product
Range:
TeSys
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Mercury Free:
Yes
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || UL 60335-1 || UL 60335-2-40:Annex JJ
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Poles Description:
4P
Ambient Air Temperature For Operation:
-25-60°C
Halogen Content Performance:
Halogen free plastic parts product
[Ith] Conventional Free Air Thermal Current:
250 A (at 40°C)
Environmental Disclosure:
ENVPEP2105013
[Ie] Rated Operational Current:
115 A (at <60°C) at <= 440 V AC-3 || 250 A (at <40°C) at <= 1000 V AC-1
Irms Rated Making Capacity:
1560 A at 440 V
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Hold-In Power Consumption In W:
5.7-5.7 W
Tightening Torque:
18 N.m
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
[Ui] Rated Insulation Voltage:
1000 V
Mechanical Durability:
8 Mcycles
China Rohs Regulation:
X
Net Weight:
5.1 kg
Eu Rohs Directive:
Compliant with Exemptions
Connection Pitch:
35 mm
Weight:
5.1 kg
Range Of Product:
TeSys Giga
$980.00

Description

TeSys Giga high power contactor, 4 poles (4 NO) for category AC-1 applications up to 250A @440V. It provides a 24-48V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 143mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.