Poles Description:
4P
Width:
143 mm
Depth:
193 mm
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Eu Rohs Directive:
Compliant with Exemptions
[Uc] Control Circuit Voltage:
200...500 V AC 50/60 Hz || 200...500 V DC
Inrush Power In Va:
295-295 VA
Hold-In Power Consumption In Va:
13.0-13.0 VA
Range Of Product:
TeSys Giga
China Rohs Regulation:
X
Circularity Profile:
ENVEOLI2105013
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Auxiliary Contact Composition:
1 NO + 1 NC
Hold-In Power Consumption In W:
8.0-8.0 W
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || UL 60335-1 || UL 60335-2-40:Annex JJ
Range:
TeSys
Halogen Content Performance:
Halogen free plastic parts product
Net Weight:
5.1 kg
Operating Time:
40...70 ms closing || 15...50 ms opening
Sustainable Offer Status:
Green Premium product
Ambient Air Temperature For Storage:
-60-80°C
Mounting Support:
plate
[Icw] Rated Short-Time Withstand Current:
1.1 kA - 10 s || 0.64 kA - 30 s || 0.52 kA - 1 min || 0.4 kA - 3 min || 0.32 kA - 10 min
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1
Mechanical Durability:
8 Mcycles
Tightening Torque:
18 N.m
Mercury Free:
Yes
Inrush Power In W:
215 W
Environmental Disclosure:
ENVPEP2105013
Utilisation Category:
AC-3 || AC-3e || AC-1 || AC-5a || AC-5b || AC-6a || AC-6b || DC-1 || DC-3 || DC-5
Product Or Component Type:
contactor
Pvc Free:
Yes
[Ie] Rated Operational Current:
115 A (at <60°C) at <= 440 V AC-3 || 250 A (at <40°C) at <= 1000 V AC-1
[Ith] Conventional Free Air Thermal Current:
250 A (at 40°C)
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Compatibility Code:
LC1G
Ambient Air Temperature For Operation:
-25-60°C
[Ui] Rated Insulation Voltage:
1000 V
Overvoltage Category:
III
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Irms Rated Making Capacity:
1560 A at 440 V
Associated Fuse Rating:
125 A aM at <= 440 V for motor || 125 A aM at <= 690 V for motor || 315 A gG at <= 690 V
Power Dissipation Per Pole:
10 W AC-1 - Ith 250 A || 3 W AC-3 - Ith 115 A
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
$980.00

Description

TeSys Giga high power contactor, 4 poles (4 NO) for category AC-1 applications up to 250A @440V. It provides a 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 143mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.