Schneider Electric

Schneider Electric LC1G115EHEN Contactor, high power, TeSys Giga, standard version, 3 pole/NO, AC-3 <=440V 115A, 48-130VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G115EHEN
MPN:
LC1G115EHEN
Condition:
New
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
Color:
dark grey
Auxiliary Contact Composition:
1 NO + 1 NC
Mechanical Durability:
8 Mcycles
Range Of Product:
TeSys Giga
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Circularity Profile:
ENVEOLI2105013
Motor Power Kw:
30 kW at 230 V AC 50/60 Hz (AC-3e) || 55 kW at 400 V AC 50/60 Hz (AC-3e) || 55 kW at 415 V AC 50/60 Hz (AC-3e) || 75 kW at 440 V AC 50/60 Hz (AC-3e) || 75 kW at 500 V AC 50/60 Hz (AC-3e) || 75 kW at 690 V AC 50/60 Hz (AC-3e) || 30 kW at 230 V AC 50/6
Power Dissipation Per Pole:
10 W AC-1 - Ith 250 A || 3 W AC-3 - Ith 115 A
[Icw] Rated Short-Time Withstand Current:
1.1 kA - 10 s || 0.64 kA - 30 s || 0.52 kA - 1 min || 0.4 kA - 3 min || 0.32 kA - 10 min
Device Short Name:
LC1G
Coil Technology:
built-in bidirectional peak limiting
Irms Rated Making Capacity:
1560 A at 440 V
Product Or Component Type:
contactor
Hold-In Power Consumption In W:
7.8-7.8 W
Poles Description:
3P
Inrush Power In W:
445 W
Depth:
193 mm
Protective Treatment:
TH
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
China Rohs Regulation:
X
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
[Ie] Rated Operational Current:
250 A (at <40°C) at <= 1000 V AC-1 || 115 A (at <60°C) at <= 440 V AC-3
[Uimp] Rated Impulse Withstand Voltage:
8 kV
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
[Ui] Rated Insulation Voltage:
1000 V
Country of Origin:
France
Maximum Horse Power Rating:
30 hp at 200/208 V 60 Hz || 40 hp at 230/240 V 60 Hz || 75 hp at 460/480 V 60 Hz || 100 hp at 575/600 V 60 Hz
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Net Weight:
3.6 kg
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Pole Contact Composition:
3 NO
Mounting Support:
plate
Connection Pitch:
35 mm
Halogen Content Performance:
Halogen free plastic parts product
Environmental Disclosure:
ENVPEP2105013
Sustainable Offer Status:
Green Premium product
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Operating Time:
40...70 ms closing || 15...50 ms opening
Eu Rohs Directive:
Compliant with Exemptions
Ambient Air Temperature For Operation:
-25-60°C
Associated Fuse Rating:
125 A aM at <= 440 V for motor || 125 A aM at <= 690 V for motor || 315 A gG at <= 690 V
Range:
TeSys
Ambient Air Temperature For Storage:
-60-80°C
Pvc Free:
Yes
$650.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 115A 75kW@440V. It provides a 48-130V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.