Schneider Electric

Schneider Electric LC1G115KUEN Contactor, high power, TeSys Giga, standard version, 3 pole/NO, AC-3 <=440V 115A, 100-250VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G115KUEN
MPN:
LC1G115KUEN
Condition:
New
Operating Time:
40...70 ms closing || 15...50 ms opening
Rated Breaking Capacity:
1040 A at 440 V
Connection Pitch:
35 mm
Protective Treatment:
TH
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Ambient Air Temperature For Storage:
-60-80°C
Hold-In Power Consumption In W:
7.8-7.8 W
Range:
TeSys
Sustainable Offer Status:
Green Premium product
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
Depth:
193 mm
China Rohs Regulation:
X
Inrush Power In Va:
540-540 VA
Weight:
3.6 kg
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Color:
dark grey
Eu Rohs Directive:
Compliant with Exemptions
Contactor Application:
power switching || motor control
Hold-In Power Consumption In Va:
12.4-12.4 VA
Rohs Exemption Information:
Yes
Power Dissipation Per Pole:
10 W AC-1 - Ith 250 A || 3 W AC-3 - Ith 115 A
Overvoltage Category:
III
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Compatibility Code:
LC1G
Mounting Support:
plate
Average Impedance:
0.00018 Ohm
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Range Of Product:
TeSys Giga
Halogen Content Performance:
Halogen free plastic parts product
[Ui] Rated Insulation Voltage:
1000 V
Pvc Free:
Yes
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Associated Fuse Rating:
125 A aM at <= 440 V for motor || 125 A aM at <= 690 V for motor || 315 A gG at <= 690 V
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Motor Power Kw:
30 kW at 230 V AC 50/60 Hz (AC-3e) || 55 kW at 400 V AC 50/60 Hz (AC-3e) || 55 kW at 415 V AC 50/60 Hz (AC-3e) || 75 kW at 440 V AC 50/60 Hz (AC-3e) || 75 kW at 500 V AC 50/60 Hz (AC-3e) || 75 kW at 690 V AC 50/60 Hz (AC-3e) || 30 kW at 230 V AC 50/6
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Inrush Power In W:
380 W
Product Or Component Type:
contactor
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8a || AC-8b || DC-1 || DC-3 || DC-5
Net Weight:
3.6 kg
Tightening Torque:
18 N.m
Auxiliary Contact Composition:
1 NO + 1 NC
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Mechanical Durability:
8 Mcycles
$650.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 115A 75kW@440V. It provides a 100-250V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose