Schneider Electric

Schneider Electric LC1G1504LSEN Contactor, high power, TeSys Giga, 4P(4NO), AC-1, <=440V 275A, standard version, 200-500V AC/DC wide band coil

(No reviews yet) Write a Review
SKU:
LC1G1504LSEN
MPN:
LC1G1504LSEN
Condition:
New
Environmental Disclosure:
ENVPEP2105013
Range Of Product:
TeSys Giga
[Uimp] Rated Impulse Withstand Voltage:
8 kV
[Uc] Control Circuit Voltage:
200...500 V AC 50/60 Hz || 200...500 V DC
Sustainable Offer Status:
Green Premium product
Overvoltage Category:
III
Circularity Profile:
ENVEOLI2105013
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Net Weight:
4.4 kg
Compatibility Code:
LC1G
Product Or Component Type:
contactor
[Ui] Rated Insulation Voltage:
1000 V
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - c
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Hold-In Power Consumption In Va:
13-13 VA
Hold-In Power Consumption In W:
8-8 W
Protective Treatment:
TH
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Poles Description:
4P
Rohs Exemption Information:
Yes
Country of Origin:
China
[Ie] Rated Operational Current:
150 A (at <60°C) at <= 440 V AC-3 || 275 A (at <40°C) at <= 1000 V AC-1
Inrush Power In W:
215 W
Auxiliary Contact Composition:
1 NO + 1 NC
[Icw] Rated Short-Time Withstand Current:
1.2 kA - 10 s || 0.7 kA - 30 s || 0.6 kA - 1 min || 0.45 kA - 3 min || 0.35 kA - 10 min
Pole Contact Composition:
4 NO
Rated Breaking Capacity:
1280 A at 440 V
Eu Rohs Directive:
Compliant with Exemptions
Mechanical Durability:
8 Mcycles
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
China Rohs Regulation:
X
Average Impedance:
0.00018 Ohm
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Contactor Application:
power switching
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Utilisation Category:
AC-3 || AC-3e || AC-1 || AC-5a || AC-5b || AC-6a || AC-6b || DC-1 || DC-3 || DC-5
Mounting Support:
plate
Power Dissipation Per Pole:
10 W AC-1 - Ith 275 A || 5 W AC-3 - Ith 150 A
Coil Technology:
built-in bidirectional peak limiting
Range:
TeSys
Mercury Free:
Yes
[Ith] Conventional Free Air Thermal Current:
275 A (at 40°C)
Associated Fuse Rating:
160 A aM at <= 440 V for motor || 160 A aM at <= 690 V for motor || 315 A gG at <= 690 V
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Color:
dark grey
Device Short Name:
LC1G
$1,110.00