Schneider Electric LC1G150KUEN Contactor, high power, TeSys Giga, standard version, 3 pole/NO, AC-3 <=440V 150A, 100-250VAC/DC coil
Schneider Electric
$740.00
TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 150A 90kW@440V. It provides a 100-250V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
- Overvoltage Category:
- III
- Mounting Support:
- plate
- Eu Rohs Directive:
- Compliant with Exemptions
- Connections - Terminals:
- power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
- Motor Power Kw:
- 37 kW at 230 V AC 50/60 Hz (AC-3e) || 75 kW at 400 V AC 50/60 Hz (AC-3e) || 75 kW at 415 V AC 50/60 Hz (AC-3e) || 90 kW at 440 V AC 50/60 Hz (AC-3e) || 90 kW at 500 V AC 50/60 Hz (AC-3e) || 90 kW at 690 V AC 50/60 Hz (AC-3e) || 75 kW at 1000 V AC 50/
- Country of Origin:
- France
- Product Certifications:
- CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
- Poles Description:
- 3P
- Safety Reliability Level:
- B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
- [Icw] Rated Short-Time Withstand Current:
- 1.2 kA - 10 s || 0.7 kA - 30 s || 0.6 kA - 1 min || 0.45 kA - 3 min || 0.35 kA - 10 min
- Compatibility Code:
- LC1G
- Tightening Torque:
- 18 N.m
- Maximum Horse Power Rating:
- 40 hp at 200/208 V 60 Hz || 50 hp at 230/240 V 60 Hz || 100 hp at 460/480 V 60 Hz || 125 hp at 575/600 V 60 Hz
- Mechanical Durability:
- 8 Mcycles
- Average Impedance:
- 0.00018 Ohm
- [Uc] Control Circuit Voltage:
- 100...250 V AC 50/60 Hz || 100...250 V DC
- Mechanical Robustness:
- vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
- Coil Technology:
- built-in bidirectional peak limiting
- Maximum Operating Rate:
- 600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
- Pole Contact Composition:
- 3 NO
- Contactor Application:
- power switching || motor control
- Power Dissipation Per Pole:
- 10 W AC-1 - Ith 275 A || 5 W AC-3 - Ith 150 A
- Connection Pitch:
- 35 mm
- Color:
- dark grey
- Permissible Ambient Air Temperature Around The Device:
- -40-70°C at Uc
- Ambient Air Temperature For Storage:
- -60-80°C
- [Ith] Conventional Free Air Thermal Current:
- 275 A (at 40°C)
- [Ie] Rated Operational Current:
- 275 A (at <40°C) at <= 1000 V AC-1 || 150 A (at <60°C) at <= 440 V AC-3
- Hold-In Power Consumption In W:
- 7.8-7.8 W
- Device Short Name:
- LC1G
- Ip Degree Of Protection:
- IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
- Sustainable Offer Status:
- Green Premium product
- Associated Fuse Rating:
- 160 A aM at <= 440 V for motor || 160 A aM at <= 690 V for motor || 315 A gG at <= 690 V
- Depth:
- 193 mm
- Mercury Free:
- Yes
- Ambient Air Temperature For Operation:
- -25-60°C
- Height:
- 193 mm
- Weight:
- 3.6 kg
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Inrush Power In W:
- 380 W
- Environmental Disclosure:
- ENVPEP2105013
- Net Weight:
- 3.6 kg
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Inrush Power In Va:
- 540-540 VA
- Operating Time:
- 40...70 ms closing || 15...50 ms opening
- Utilisation Category:
- AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8a || AC-8b || DC-1 || DC-3 || DC-5
- Range:
- TeSys