Schneider Electric LC1G1854LSEN Contactor, high power, TeSys Giga, 4P(4NO), AC-1, <=440V 305A, standard version, 200-500V AC/DC wide band coil
Schneider Electric
$1,280.00
Contactor, high power, TeSys Giga, 4P(4NO), AC-1, <=440V 305A, standard version, 200-500V AC/DC wide band coil
- Eu Rohs Directive:
- Compliant with Exemptions
- Inrush Power In Va:
- 295-295 VA
- [Icw] Rated Short-Time Withstand Current:
- 1.5 kA - 10 s || 0.92 kA - 30 s || 0.74 kA - 1 min || 0.5 kA - 3 min || 0.4 kA - 10 min
- Weight:
- 4.4 kg
- Ambient Air Temperature For Operation:
- -25-60°C
- [Ith] Conventional Free Air Thermal Current:
- 305 A (at 40°C)
- Pole Contact Composition:
- 4 NO
- Ip Degree Of Protection:
- IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
- Range:
- TeSys
- Connections - Terminals:
- power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² - c
- [Ue] Rated Operational Voltage:
- <= 1000 V AC 50/60 Hz || <= 460 V DC
- Circularity Profile:
- ENVEOLI2105013
- Operating Time:
- 40...70 ms closing || 15...50 ms opening
- Mercury Free:
- Yes
- Hold-In Power Consumption In W:
- 8-8 W
- Safety Reliability Level:
- B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
- Hold-In Power Consumption In Va:
- 13-13 VA
- Tightening Torque:
- 18 N.m
- Power Dissipation Per Pole:
- 20 W AC-1 - Ith 305 A || 6 W AC-3 - Ith 185 A
- Associated Fuse Rating:
- 200 A aM at <= 440 V for motor || 160 A aM at <= 690 V for motor || 315 A gG at <= 690 V
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- China Rohs Regulation:
- X
- Environmental Disclosure:
- ENVPEP2105013
- Width:
- 143 mm
- Coil Technology:
- built-in bidirectional peak limiting
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
- Country of Origin:
- China
- Sustainable Offer Status:
- Green Premium product
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || UL 60335-1 || UL 60335-2-40:Annex JJ
- Mechanical Durability:
- 8 Mcycles
- Depth:
- 193 mm
- Inrush Power In W:
- 215 W
- Poles Description:
- 4P
- Mounting Support:
- plate
- Product Certifications:
- CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
- [Ui] Rated Insulation Voltage:
- 1000 V
- Color:
- dark grey
- Permissible Ambient Air Temperature Around The Device:
- -40-70°C at Uc
- Rated Breaking Capacity:
- 1610 A at 440 V
- Compatibility Code:
- LC1G
- Product Or Component Type:
- contactor
- Average Impedance:
- 0.00017 Ohm
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Ambient Air Temperature For Storage:
- -60-80°C
- Control Circuit Voltage Limits:
- operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
- Contactor Application:
- power switching
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Mechanical Robustness:
- vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed