Schneider Electric

Schneider Electric LC1G225LSEA Contactor, high power, TeSys Giga, advanced version, 3 pole/NO, AC-3 <=440V 225A, 200-500VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G225LSEA
MPN:
LC1G225LSEA
Condition:
New
Associated Fuse Rating:
250 A aM at <= 440 V for motor || 200 A aM at <= 690 V for motor || 400 A gG at <= 690 V
Inrush Power In W:
215 W
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
Power Dissipation Per Pole:
20 W AC-1 - Ith 330 A || 8 W AC-3 - Ith 225 A
Maximum Horse Power Rating:
60 hp at 200/208 V 60 Hz || 75 hp at 230/240 V 60 Hz || 150 hp at 460/480 V 60 Hz || 150 hp at 575/600 V 60 Hz
Hold-In Power Consumption In Va:
13.0-13.0 VA
[Ie] Rated Operational Current:
330 A (at <40°C) at <= 1000 V AC-1 || 225 A (at <60°C) at <= 440 V AC-3
Width:
108 mm
[Icw] Rated Short-Time Withstand Current:
1.8 kA - 10 s || 1.0 kA - 30 s || 0.85 kA - 1 min || 0.56 kA - 3 min || 0.44 kA - 10 min
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Weight:
4.1 kg
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Halogen Content Performance:
Halogen free plastic parts product
Circularity Profile:
ENVEOLI2105013
Range:
TeSys
Eu Rohs Directive:
Compliant with Exemptions
Mounting Support:
plate
Device Short Name:
LC1G
Pvc Free:
Yes
Mercury Free:
Yes
Operating Time:
40...70 ms closing || 15...50 ms opening
[Ui] Rated Insulation Voltage:
1000 V
Range Of Product:
TeSys Giga
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Poles Description:
3P
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Rated Breaking Capacity:
2050 A at 440 V
China Rohs Regulation:
X
Connection Pitch:
35 mm
Pole Contact Composition:
3 NO
Hold-In Power Consumption In W:
8.0-8.0 W
Compatibility Code:
LC1G
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Protective Treatment:
TH
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 25 x 6 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Color:
dark grey
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
Tightening Torque:
18 N.m
Overvoltage Category:
III
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application:
power switching || motor control
Product Or Component Type:
contactor
Environmental Disclosure:
ENVPEP2105013
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Rohs Exemption Information:
Yes
[Uc] Control Circuit Voltage:
200...500 V AC 50/60 Hz || 200...500 V DC
Auxiliary Contact Composition:
1 NO + 1 NC
$1,330.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 225A 132kW@440V. It provides a 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 255mm x 108mm x 175mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose