Schneider Electric

Schneider Electric LC1G265LSEN Contactor, high power, TeSys Giga, 3P(3NO), AC-3, <=440V 265A, standard version, 200-500V AC/DC wide band coil

(No reviews yet) Write a Review
SKU:
LC1G265LSEN
MPN:
LC1G265LSEN
Condition:
New
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8a || AC-8b || DC-1 || DC-3 || DC-5
Operating Time:
40...70 ms closing || 15...50 ms opening
Ambient Air Temperature For Operation:
-25-60°C
Country of Origin:
China
Net Weight:
7.5 kg
Rohs Exemption Information:
Yes
[Ie] Rated Operational Current:
385 A (at <40°C) at <= 1000 V AC-1 || 265 A (at <60°C) at <= 440 V AC-3
Irms Rated Making Capacity:
3320 A at 440 V
Motor Power Kw:
75 kW at 230 V AC 50/60 Hz (AC-3e) || 132 kW at 400 V AC 50/60 Hz (AC-3e) || 132 kW at 415 V AC 50/60 Hz (AC-3e) || 160 kW at 440 V AC 50/60 Hz (AC-3e) || 160 kW at 500 V AC 50/60 Hz (AC-3e) || 200 kW at 690 V AC 50/60 Hz (AC-3e) || 160 kW at 1000 V
Hold-In Power Consumption In Va:
16.1-16.1 VA
Average Impedance:
0.000144 Ohm
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
[Icw] Rated Short-Time Withstand Current:
2.2 kA - 10 s || 1.23 kA - 30 s || 0.95 kA - 1 min || 0.62 kA - 3 min || 0.48 kA - 10 min
Mercury Free:
Yes
Inrush Power In W:
300 W
Connection Pitch:
45 mm
Pole Contact Composition:
3 NO
Ambient Air Temperature For Storage:
-60-80°C
[Ui] Rated Insulation Voltage:
1000 V
Circularity Profile:
ENVEOLI2105013
Product Or Component Type:
contactor
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Depth:
226 mm
Width:
140 mm
[Ith] Conventional Free Air Thermal Current:
385 A (at 40°C)
Poles Description:
3P
Range Of Product:
TeSys Giga
Overvoltage Category:
III
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Color:
dark grey
China Rohs Regulation:
X
Mechanical Durability:
8 Mcycles
Contactor Application:
power switching || motor control
Power Dissipation Per Pole:
20 W AC-1 - Ith 385 A || 11 W AC-3 - Ith 265 A
Protective Treatment:
TH
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Coil Technology:
built-in bidirectional peak limiting
Associated Fuse Rating:
315 A aM at <= 440 V for motor || 250 A aM at <= 690 V for motor || 400 A gG at <= 690 V
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Device Short Name:
LC1G
Tightening Torque:
35 N.m
Weight:
7.5 kg
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Mounting Support:
plate
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
$1,570.00