Schneider Electric

Schneider Electric LC1G3304KUEN Contactor, high power, TeSys Giga, standard version, 4 pole/NO, AC-1 <=440V 440A, 100-250VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G3304KUEN
MPN:
LC1G3304KUEN
Condition:
New
Pole Contact Composition:
4 NO
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Compatibility Code:
LC1G
Tightening Torque:
35 N.m
Contactor Application:
power switching
Pvc Free:
Yes
Mounting Support:
plate
Product Or Component Type:
contactor
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 32 x 10 mm || power circuit: lugs-ring terminals 1 185-185 mm² || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control circuit: push-in 1 0.25-2.5 mm² -
Ambient Air Temperature For Operation:
-25-60°C
Inrush Power In W:
645 W
Coil Technology:
built-in bidirectional peak limiting
Rated Breaking Capacity:
2940 A at 440 V
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
China Rohs Regulation:
X
[Icw] Rated Short-Time Withstand Current:
2.65 kA - 10 s || 1.8 kA - 30 s || 1.3 kA - 1 min || 0.9 kA - 3 min || 0.75 kA - 10 min
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
[Ie] Rated Operational Current:
330 A (at <60°C) at <= 440 V AC-3 || 440 A (at <40°C) at <= 1000 V AC-1
Circularity Profile:
ENVEOLI2105013
Associated Fuse Rating:
400 A aM at <= 440 V for motor || 250 A aM at <= 690 V for motor || 500 A gG at <= 690 V
Inrush Power In Va:
700-700 VA
Weight:
8.2 kg
Protective Treatment:
TH
Hold-In Power Consumption In W:
9.1-9.1 W
[Uimp] Rated Impulse Withstand Voltage:
8 kV
[Uc] Control Circuit Voltage:
100...250 V AC 50/60 Hz || 100...250 V DC
Net Weight:
8.2 kg
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Color:
dark grey
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || UL 60335-1 || UL 60335-2-40:Annex JJ
[Ith] Conventional Free Air Thermal Current:
440 A (at 40°C)
Country of Origin:
China
Power Dissipation Per Pole:
30 W AC-1 - Ith 440 A || 16 W AC-3 - Ith 330 A
Poles Description:
4P
Hold-In Power Consumption In Va:
15.0-15.0 VA
Operating Time:
40...70 ms closing || 15...50 ms opening
Average Impedance:
0.000144 Ohm
Range:
TeSys
Mercury Free:
Yes
Device Short Name:
LC1G
Ambient Air Temperature For Storage:
-60-80°C
Eu Rohs Directive:
Compliant with Exemptions
Overvoltage Category:
III
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Sustainable Offer Status:
Green Premium product
Rohs Exemption Information:
Yes
$1,950.00

Description

TeSys Giga high power contactor, 4 poles (4 NO) for category AC-1 applications up to 440A @440V. It provides a 100-250V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 290mm x 185mm x 209mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose