Schneider Electric

Schneider Electric LC1G330EHEN Contactor, high power, TeSys Giga, standard version, 3 pole/NO, AC-3 <=440V 330A, 48-130VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G330EHEN
MPN:
LC1G330EHEN
Condition:
New
Circularity Profile:
ENVEOLI2105013
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Inrush Power In Va:
780-780 VA
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Protective Treatment:
TH
Coil Technology:
built-in bidirectional peak limiting
Range Of Product:
TeSys Giga
Weight:
7.5 kg
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Hold-In Power Consumption In Va:
17.6-17.6 VA
Connection Pitch:
45 mm
Halogen Content Performance:
Halogen free plastic parts product
Average Impedance:
0.000144 Ohm
Overvoltage Category:
III
Pvc Free:
Yes
Mercury Free:
Yes
Eu Rohs Directive:
Compliant with Exemptions
Rated Breaking Capacity:
2940 A at 440 V
Width:
140 mm
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
[Ie] Rated Operational Current:
440 A (at <40°C) at <= 1000 V AC-1 || 330 A (at <60°C) at <= 440 V AC-3
Operating Time:
40...70 ms closing || 15...50 ms opening
Contactor Application:
power switching || motor control
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 32 x 10 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Environmental Disclosure:
ENVPEP2105013
Rohs Exemption Information:
Yes
Net Weight:
7.5 kg
Device Short Name:
LC1G
Pole Contact Composition:
3 NO
Range:
TeSys
Ambient Air Temperature For Operation:
-25-60°C
Maximum Horse Power Rating:
100 hp at 200/208 V 60 Hz || 125 hp at 230/240 V 60 Hz || 250 hp at 460/480 V 60 Hz || 300 hp at 575/600 V 60 Hz
Hold-In Power Consumption In W:
7.8-7.8 W
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
Tightening Torque:
35 N.m
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Irms Rated Making Capacity:
3830 A at 440 V
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Compatibility Code:
LC1G
Associated Fuse Rating:
400 A aM at <= 440 V for motor || 250 A aM at <= 690 V for motor || 500 A gG at <= 690 V
Inrush Power In W:
695 W
Depth:
226 mm
Mechanical Durability:
8 Mcycles
Auxiliary Contact Composition:
1 NO + 1 NC
Mounting Support:
plate
Poles Description:
3P
$1,495.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 330A 200kW@440V. It provides a 48-130V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 290mm x 140mm x 209mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose