Schneider Electric

Schneider Electric LC1G400BEEA Contactor, high power, TeSys Giga, advanced version, AC-3, <= 440V, 400A, 3 pole/NO, 24-48VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G400BEEA
MPN:
LC1G400BEEA
Condition:
New
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Rated Breaking Capacity:
3480 A at 440 V
Device Short Name:
LC1G
Associated Fuse Rating:
500 A aM at <= 440 V for motor || 315 A aM at <= 690 V for motor || 630 A gG at <= 690 V
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
[Icw] Rated Short-Time Withstand Current:
3.6 kA - 10 s || 2.4 kA - 30 s || 1.7 kA - 1 min || 1.2 kA - 3 min || 1.0 kA - 10 min
Ambient Air Temperature For Operation:
-25-60°C
Protective Treatment:
TH
Motor Power Kw:
110 kW at 230 V AC 50/60 Hz (AC-3e) || 200 kW at 400 V AC 50/60 Hz (AC-3e) || 200 kW at 415 V AC 50/60 Hz (AC-3e) || 250 kW at 440 V AC 50/60 Hz (AC-3e) || 250 kW at 500 V AC 50/60 Hz (AC-3e) || 315 kW at 690 V AC 50/60 Hz (AC-3e) || 220 kW at 1000 V
Ambient Air Temperature For Storage:
-60-80°C
[Ith] Conventional Free Air Thermal Current:
550 A (at 40°C)
Halogen Content Performance:
Halogen free plastic parts product
Operating Time:
40...70 ms closing || 15...50 ms opening
Power Dissipation Per Pole:
30 W AC-1 - Ith 550 A || 16 W AC-3 - Ith 400 A
Poles Description:
3P
Maximum Horse Power Rating:
125 hp at 200/208 V 60 Hz || 150 hp at 230/240 V 60 Hz || 300 hp at 460/480 V 60 Hz || 400 hp at 575/600 V 60 Hz
[Ui] Rated Insulation Voltage:
1000 V
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Net Weight:
8.2 kg
Depth:
226 mm
Mercury Free:
Yes
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Mounting Support:
plate
Color:
dark grey
Country of Origin:
China
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8a || AC-8b || DC-1 || DC-3 || DC-5
China Rohs Regulation:
X
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Auxiliary Contact Composition:
1 NO + 1 NC
Range Of Product:
TeSys Giga
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Range:
TeSys
[Ie] Rated Operational Current:
550 A (at <40°C) at <= 1000 V AC-1 || 400 A (at <60°C) at <= 440 V AC-3
Tightening Torque:
35 N.m
Product Or Component Type:
contactor
Connection Pitch:
45 mm
Pole Contact Composition:
3 NO
Height:
290 mm
Hold-In Power Consumption In Va:
17.9-17.9 VA
Coil Technology:
built-in bidirectional peak limiting
Rohs Exemption Information:
Yes
Pvc Free:
Yes
Compatibility Code:
LC1G
[Uc] Control Circuit Voltage:
24...48 V AC 50/60 Hz || 24...48 V DC
$1,970.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 400A 250kW@440V. It provides a 24-48V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 290mm x 140mm x 209mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.