Schneider Electric

Schneider Electric LC1G400EHEA Contactor, high power, TeSys Giga, advanced version, AC-3, <= 440V, 400A, 3 pole/NO, 48-130VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G400EHEA
MPN:
LC1G400EHEA
Condition:
New
Auxiliary Contact Composition:
1 NO + 1 NC
[Uimp] Rated Impulse Withstand Voltage:
8 kV
China Rohs Regulation:
X
Mechanical Durability:
8 Mcycles
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Net Weight:
8.2 kg
Pole Contact Composition:
3 NO
Range Of Product:
TeSys Giga
Contactor Application:
power switching || motor control
[Ith] Conventional Free Air Thermal Current:
550 A (at 40°C)
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Associated Fuse Rating:
500 A aM at <= 440 V for motor || 315 A aM at <= 690 V for motor || 630 A gG at <= 690 V
Sustainable Offer Status:
Green Premium product
Eu Rohs Directive:
Compliant with Exemptions
Tightening Torque:
35 N.m
Rated Breaking Capacity:
3480 A at 440 V
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
Pvc Free:
Yes
[Icw] Rated Short-Time Withstand Current:
3.6 kA - 10 s || 2.4 kA - 30 s || 1.7 kA - 1 min || 1.2 kA - 3 min || 1.0 kA - 10 min
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Maximum Horse Power Rating:
125 hp at 200/208 V 60 Hz || 150 hp at 230/240 V 60 Hz || 300 hp at 460/480 V 60 Hz || 400 hp at 575/600 V 60 Hz
Ambient Air Temperature For Storage:
-60-80°C
Hold-In Power Consumption In W:
8.3-8.3 W
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Environmental Disclosure:
ENVPEP2105013
Ambient Air Temperature For Operation:
-25-60°C
Inrush Power In W:
360 W
Overvoltage Category:
III
Operating Time:
40...70 ms closing || 15...50 ms opening
Poles Description:
3P
Circularity Profile:
ENVEOLI2105013
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Protective Treatment:
TH
Power Dissipation Per Pole:
30 W AC-1 - Ith 550 A || 16 W AC-3 - Ith 400 A
Weight:
8.2 kg
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
[Uc] Control Circuit Voltage:
48...130 V AC 50/60 Hz || 48...130 V DC
Halogen Content Performance:
Halogen free plastic parts product
[Ui] Rated Insulation Voltage:
1000 V
Mounting Support:
plate
Device Short Name:
LC1G
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Depth:
226 mm
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
$1,970.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 400A 250kW@440V. It provides a 48-130V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 290mm x 140mm x 209mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.