Schneider Electric

Schneider Electric LC1G400EHEN Contactor, high power, TeSys Giga, standard version, 3 pole/NO, AC-3 <=440V 400A, 48-130VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G400EHEN
MPN:
LC1G400EHEN
Condition:
New
Country of Origin:
France
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Depth:
226 mm
Overvoltage Category:
III
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Color:
dark grey
Sustainable Offer Status:
Green Premium product
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 32 x 10 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Connection Pitch:
45 mm
Hold-In Power Consumption In Va:
17.6-17.6 VA
Width:
140 mm
Ambient Air Temperature For Operation:
-25-60°C
Environmental Disclosure:
ENVPEP2105013
Pole Contact Composition:
3 NO
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ith] Conventional Free Air Thermal Current:
550 A (at 40°C)
Compatibility Code:
LC1G
Associated Fuse Rating:
500 A aM at <= 440 V for motor || 315 A aM at <= 690 V for motor || 630 A gG at <= 690 V
Net Weight:
7.5 kg
Contactor Application:
power switching || motor control
Range Of Product:
TeSys Giga
Power Dissipation Per Pole:
30 W AC-1 - Ith 550 A || 16 W AC-3 - Ith 400 A
Tightening Torque:
35 N.m
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Range:
TeSys
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Rohs Exemption Information:
Yes
Halogen Content Performance:
Halogen free plastic parts product
Maximum Horse Power Rating:
125 hp at 200/208 V 60 Hz || 150 hp at 230/240 V 60 Hz || 300 hp at 460/480 V 60 Hz || 400 hp at 575/600 V 60 Hz
Auxiliary Contact Composition:
1 NO + 1 NC
Circularity Profile:
ENVEOLI2105013
Average Impedance:
0.0001 Ohm
Hold-In Power Consumption In W:
7.8-7.8 W
Irms Rated Making Capacity:
5090 A at 440 V
Product Or Component Type:
contactor
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Protective Treatment:
TH
China Rohs Regulation:
X
[Icw] Rated Short-Time Withstand Current:
3.6 kA - 10 s || 2.4 kA - 30 s || 1.7 kA - 1 min || 1.2 kA - 3 min || 1.0 kA - 10 min
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Mechanical Durability:
8 Mcycles
Operating Time:
40...70 ms closing || 15...50 ms opening
Mercury Free:
Yes
[Ie] Rated Operational Current:
550 A (at <40°C) at <= 1000 V AC-1 || 400 A (at <60°C) at <= 440 V AC-3
Device Short Name:
LC1G
Inrush Power In W:
760 W
Height:
225 mm
Weight:
7.5 kg
[Uc] Control Circuit Voltage:
48...130 V AC 50/60 Hz || 48...130 V DC
$1,710.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 400A 250kW@440V. It provides a 48-130V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 290mm x 140mm x 209mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose