Schneider Electric

Schneider Electric LC1G400LSEN Contactor, high power, TeSys Giga, 3P(3NO), AC-3, <=440V 400A, standard version, 200-500V AC/DC wide band coil

(No reviews yet) Write a Review
SKU:
LC1G400LSEN
MPN:
LC1G400LSEN
Condition:
New
Circularity Profile:
ENVEOLI2105013
Operating Time:
40...70 ms closing || 15...50 ms opening
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Pole Contact Composition:
3 NO
[Icw] Rated Short-Time Withstand Current:
3.6 kA - 10 s || 2.4 kA - 30 s || 1.7 kA - 1 min || 1.2 kA - 3 min || 1.0 kA - 10 min
Net Weight:
7.5 kg
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Poles Description:
3P
China Rohs Regulation:
X
Mounting Support:
plate
Mercury Free:
Yes
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Contactor Application:
power switching || motor control
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
Protective Treatment:
TH
Color:
dark grey
Compatibility Code:
LC1G
Tightening Torque:
35 N.m
Mechanical Durability:
8 Mcycles
Inrush Power In Va:
535-535 VA
Irms Rated Making Capacity:
5090 A at 440 V
Auxiliary Contact Composition:
1 NO + 1 NC
Depth:
226 mm
[Ith] Conventional Free Air Thermal Current:
550 A (at 40°C)
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Power Dissipation Per Pole:
30 W AC-1 - Ith 550 A || 16 W AC-3 - Ith 400 A
Ambient Air Temperature For Operation:
-25-60°C
Maximum Horse Power Rating:
125 hp at 200/208 V 60 Hz || 150 hp at 230/240 V 60 Hz || 300 hp at 460/480 V 60 Hz || 400 hp at 575/600 V 60 Hz
Country of Origin:
China
[Ie] Rated Operational Current:
550 A (at <40°C) at <= 1000 V AC-1 || 400 A (at <60°C) at <= 440 V AC-3
Device Short Name:
LC1G
Associated Fuse Rating:
500 A aM at <= 440 V for motor || 315 A aM at <= 690 V for motor || 630 A gG at <= 690 V
Product Or Component Type:
contactor
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8a || AC-8b || DC-1 || DC-3 || DC-5
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Coil Technology:
built-in bidirectional peak limiting
Motor Power Kw:
110 kW at 230 V AC 50/60 Hz (AC-3e) || 200 kW at 400 V AC 50/60 Hz (AC-3e) || 200 kW at 415 V AC 50/60 Hz (AC-3e) || 250 kW at 440 V AC 50/60 Hz (AC-3e) || 250 kW at 500 V AC 50/60 Hz (AC-3e) || 315 kW at 690 V AC 50/60 Hz (AC-3e) || 220 kW at 1000 V
Connection Pitch:
45 mm
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 32 x 10 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Weight:
7.5 kg
Average Impedance:
0.0001 Ohm
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
$1,970.00