Schneider Electric

Schneider Electric LC1G5004LSEA Contactor, high power, TeSys Giga, advanced version, 4 pole/NO, AC-1 <=440V 700A, 200-500VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G5004LSEA
MPN:
LC1G5004LSEA
Condition:
New
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Rohs Exemption Information:
Yes
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Connection Pitch:
45 mm
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 32 x 10 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Range:
TeSys
Mechanical Durability:
8 Mcycles
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Rated Breaking Capacity:
4600 A at 440 V
Product Or Component Type:
contactor
Environmental Disclosure:
ENVPEP2105013
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Color:
dark grey
Protective Treatment:
TH
Country of Origin:
China
[Ie] Rated Operational Current:
500 A (at <60°C) at <= 440 V AC-3 || 700 A (at <40°C) at <= 1000 V AC-1
[Ith] Conventional Free Air Thermal Current:
700 A (at 40°C)
Device Short Name:
LC1G
Range Of Product:
TeSys Giga
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || UL 60335-1 || UL 60335-2-40:Annex JJ
Average Impedance:
0.00008 Ohm
[Uc] Control Circuit Voltage:
200...500 V AC 50/60 Hz || 200...500 V DC
Mercury Free:
Yes
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Halogen Content Performance:
Halogen free plastic parts product
[Icw] Rated Short-Time Withstand Current:
4.0 kA - 10 s || 2.8 kA - 30 s || 2.2 kA - 1 min || 1.5 kA - 3 min || 1.2 kA - 10 min
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Contactor Application:
power switching
Overvoltage Category:
III
Power Dissipation Per Pole:
40 W AC-1 - Ith 700 A || 20 W AC-3 - Ith 500 A
Ambient Air Temperature For Operation:
-25-60°C
China Rohs Regulation:
X
Pvc Free:
Yes
Inrush Power In Va:
535-535 VA
Pole Contact Composition:
4 NO
Width:
185 mm
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Operating Time:
40...70 ms closing || 15...50 ms opening
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Net Weight:
8.7 kg
Auxiliary Contact Composition:
1 NO + 1 NC
Irms Rated Making Capacity:
5090 A at 440 V
Coil Technology:
built-in bidirectional peak limiting
Hold-In Power Consumption In W:
8.6-8.6 W
Poles Description:
4P
Tightening Torque:
35 N.m
Mounting Support:
plate
[Ui] Rated Insulation Voltage:
1000 V
Height:
290 mm
$3,840.00

Description

TeSys Giga high power contactor, 4 poles (4 NO) for category AC-1 applications up to 700A @440V. It provides a 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 290mm x 185mm x 209mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose