Schneider Electric

Schneider Electric LC1G500BEEA Contactor, high power, TeSys Giga, advanced version, AC-3, <= 440V, 500A, 3 pole/NO, 24-48VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G500BEEA
MPN:
LC1G500BEEA
Condition:
New
Maximum Horse Power Rating:
150 hp at 200/208 V 60 Hz || 200 hp at 230/240 V 60 Hz || 400 hp at 460/480 V 60 Hz || 450 hp at 575/600 V 60 Hz
Weight:
8.2 kg
Power Dissipation Per Pole:
40 W AC-1 - Ith 700 A || 20 W AC-3 - Ith 500 A
Device Short Name:
LC1G
Net Weight:
8.2 kg
Protective Treatment:
TH
Rohs Exemption Information:
Yes
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 32 x 10 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Circularity Profile:
ENVEOLI2105013
Safety Reliability Level:
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Connection Pitch:
45 mm
Ambient Air Temperature For Operation:
-25-60°C
Range:
TeSys
Environmental Disclosure:
ENVPEP2105013
Irms Rated Making Capacity:
5090 A at 440 V
Color:
dark grey
Hold-In Power Consumption In W:
6.0-6.0 W
Motor Power Kw:
147 kW at 230 V AC 50/60 Hz (AC-3e) || 250 kW at 400 V AC 50/60 Hz (AC-3e) || 250 kW at 415 V AC 50/60 Hz (AC-3e) || 280 kW at 440 V AC 50/60 Hz (AC-3e) || 315 kW at 500 V AC 50/60 Hz (AC-3e) || 355 kW at 690 V AC 50/60 Hz (AC-3e) || 335 kW at 1000 V
Depth:
226 mm
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Inrush Power In W:
350 W
Ambient Air Temperature For Storage:
-60-80°C
[Ie] Rated Operational Current:
700 A (at <40°C) at <= 1000 V AC-1 || 500 A (at <60°C) at <= 440 V AC-3
Pvc Free:
Yes
Mechanical Durability:
8 Mcycles
Rated Breaking Capacity:
4600 A at 440 V
Compatibility Code:
LC1G
Operating Time:
40...70 ms closing || 15...50 ms opening
Mercury Free:
Yes
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8a || AC-8b || DC-1 || DC-3 || DC-5
Contactor Application:
power switching || motor control
Average Impedance:
0.00008 Ohm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Tightening Torque:
35 N.m
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
China Rohs Regulation:
X
[Ui] Rated Insulation Voltage:
1000 V
Associated Fuse Rating:
500 A aM at <= 440 V for motor || 400 A aM at <= 690 V for motor || 800 A gG at <= 690 V
Hold-In Power Consumption In Va:
17.9-17.9 VA
Country of Origin:
China
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Range Of Product:
TeSys Giga
Mounting Support:
plate
$2,950.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 500A 315kW@440V. It provides a 24-48V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 290mm x 140mm x 209mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.