Schneider Electric

Schneider Electric LC1G630KUEN Contactor, high power, TeSys Giga, standard version, AC-3, <= 440V, 630A, 3 pole/NO, 100-250VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G630KUEN
MPN:
LC1G630KUEN
Condition:
New
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Power Dissipation Per Pole:
70 W AC-1 - Ith 1050 A || 26 W AC-3 - Ith 630 A
Hold-In Power Consumption In W:
9.5-9.5 W
Color:
dark grey
Sustainable Offer Status:
Green Premium product
Pole Contact Composition:
3 NO
China Rohs Regulation:
X
Hold-In Power Consumption In Va:
15.0-15.0 VA
[Ie] Rated Operational Current:
1050 A (at <40°C) at <= 1000 V AC-1 || 630 A (at <60°C) at <= 440 V AC-3
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Compatibility Code:
LC1G
Associated Fuse Rating:
630 A aM at <= 440 V for motor || 500 A aM at <= 690 V for motor || 1250 A gG at <= 690 V
Maximum Horse Power Rating:
250 hp at 200/208 V 60 Hz || 300 hp at 230/240 V 60 Hz || 600 hp at 460/480 V 60 Hz || 700 hp at 575/600 V 60 Hz
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Weight:
14.2 kg
[Uc] Control Circuit Voltage:
100...250 V AC 50/60 Hz || 100...250 V DC
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 52 x 20 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Country of Origin:
France
Device Short Name:
LC1G
Mounting Support:
plate
Poles Description:
3P
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Mercury Free:
Yes
Operating Time:
40...70 ms closing || 15...50 ms opening
Connection Pitch:
70 mm
Auxiliary Contact Composition:
1 NO + 1 NC
Range Of Product:
TeSys Giga
Motor Power Kw:
180 kW at 230 V AC 50/60 Hz (AC-3e) || 315 kW at 400 V AC 50/60 Hz (AC-3e) || 335 kW at 415 V AC 50/60 Hz (AC-3e) || 355 kW at 440 V AC 50/60 Hz (AC-3e) || 375 kW at 500 V AC 50/60 Hz (AC-3e) || 500 kW at 690 V AC 50/60 Hz (AC-3e) || 450 kW at 1000 V
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Mechanical Durability:
5 Mcycles
Product Or Component Type:
contactor
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Ambient Air Temperature For Operation:
-25-60°C
Net Weight:
14.2 kg
Eu Rohs Directive:
Compliant with Exemptions
Rated Breaking Capacity:
5550 A at 440 V
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
Safety Reliability Level:
B10d = 100000 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 1800000 cycles contactor with mechanical load EN/ISO 13849-1
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Protective Treatment:
TH
Depth:
266 mm
Contactor Application:
power switching || motor control
Rohs Exemption Information:
Yes
Halogen Content Performance:
Halogen free plastic parts product
Inrush Power In W:
680 W
Inrush Power In Va:
800-800 VA
Coil Technology:
built-in bidirectional peak limiting
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8a || AC-8b || DC-1 || DC-3 || DC-5
$3,250.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 630A 400kW@440V. It provides a 100-250V AC/DC wide band low consumption electronic coil and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 324mm x 210mm x 248mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose