Schneider Electric

Schneider Electric LC1G630LSEA Contactor, high power, TeSys Giga, advanced version, AC-3, <= 440V, 630A, 3 pole/NO, 200-500VAC/DC coil

(No reviews yet) Write a Review
SKU:
LC1G630LSEA
MPN:
LC1G630LSEA
Condition:
New
Environmental Disclosure:
ENVPEP2105013
Halogen Content Performance:
Halogen free plastic parts product
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8b || AC-8a || DC-1 || DC-3 || DC-5
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Average Impedance:
0.000065 Ohm
Contactor Application:
power switching || motor control
Compatibility Code:
LC1G
Hold-In Power Consumption In Va:
17.0-17.0 VA
Standards:
EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || JIS C8201-5-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-1 || UL 60335-2-40:Annex JJ
Mechanical Durability:
5 Mcycles
Product Or Component Type:
contactor
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Circularity Profile:
ENVEOLI2105013
Ambient Air Temperature For Operation:
-25-60°C
Connection Pitch:
70 mm
Overvoltage Category:
III
Coil Technology:
built-in bidirectional peak limiting
Rohs Exemption Information:
Yes
Rated Breaking Capacity:
5550 A at 440 V
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Weight:
17.3 kg
Protective Treatment:
TH
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Inrush Power In W:
390 W
Associated Fuse Rating:
630 A aM at <= 440 V for motor || 500 A aM at <= 690 V for motor || 1250 A gG at <= 690 V
China Rohs Regulation:
X
Maximum Horse Power Rating:
250 hp at 200/208 V 60 Hz || 300 hp at 230/240 V 60 Hz || 600 hp at 460/480 V 60 Hz || 700 hp at 575/600 V 60 Hz
Country of Origin:
China
Hold-In Power Consumption In W:
11.0-11.0 W
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Tightening Torque:
58 N.m
[Ie] Rated Operational Current:
1050 A (at <40°C) at <= 1000 V AC-1 || 630 A (at <60°C) at <= 440 V AC-3
Motor Power Kw:
180 kW at 230 V AC 50/60 Hz (AC-3e) || 315 kW at 400 V AC 50/60 Hz (AC-3e) || 335 kW at 415 V AC 50/60 Hz (AC-3e) || 355 kW at 440 V AC 50/60 Hz (AC-3e) || 375 kW at 500 V AC 50/60 Hz (AC-3e) || 500 kW at 690 V AC 50/60 Hz (AC-3e) || 450 kW at 1000 V
California Proposition 65:
WARNING: This product can expose you to chemicals including: Styrene, which is known to the State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. For m
Mercury Free:
Yes
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Color:
dark grey
Sustainable Offer Status:
Green Premium product
Inrush Power In Va:
670-670 VA
Power Dissipation Per Pole:
70 W AC-1 - Ith 1050 A || 26 W AC-3 - Ith 630 A
[Icw] Rated Short-Time Withstand Current:
5.05 kA - 10 s || 4.4 kA - 30 s || 3.4 kA - 1 min || 2.2 kA - 3 min || 1.6 kA - 10 min
[Uc] Control Circuit Voltage:
200...500 V AC 50/60 Hz || 200...500 V DC
Pvc Free:
Yes
Range:
TeSys
Operating Time:
40...70 ms closing || 15...50 ms opening
$3,950.00

Description

TeSys Giga high power contactor, 3 poles (3 NO) for category AC-3 applications up to 630A 400kW@440V. It provides a 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded highly reliability 1NO+1NC auxiliary contact block (17V 1mA). Designed for demanding applications with maximum operating rates up to 600 cycles per hour and environments until 60°C. It procures high reliability and durability with 5 Mcycles mechanical durability. Local and Remote Contact Wear Diagnosis (CWD) as standard function, continuous monitoring with healthy and alarm indicators. It is possibility to replace switching module (main contacts), enhancement contactor life. Contactor can be fixed in all quadrants, maintenance without removing cables/busbars, and OLR could be directly mounted below contactor. To be used with power connection by bolted connection with cable memory kit and control connections by spring terminals, accessible from front for easy and quick replacement. It provides IP2x protection in Front face with shrouds conforming to IEC 60529 and VDE 0106. It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, No derating up to 3000m altitude. The dimension is 324mm x 210mm x 248mm (H x W x D), compact size enables panel space savings. Multi standards certified(CE,CB,CCC,cULus,EAC,KC,RCM,Marine) and Green Premium compliant (RoHs/Reach). Unique QR code provides quick access to complete product data.
View AllClose