Schneider Electric

Schneider Electric LC1G630LSEN Contactor, high power, TeSys Giga, 3P(3NO), AC-3, <=440V 630A, standard version, 200-500V AC/DC wide band coil

(No reviews yet) Write a Review
SKU:
LC1G630LSEN
MPN:
LC1G630LSEN
Condition:
New
Ambient Air Temperature For Storage:
-60-80°C
Permissible Ambient Air Temperature Around The Device:
-40-70°C at Uc
Rohs Exemption Information:
Yes
Product Certifications:
CB Scheme || CCC || cULus || EAC || CE || UKCA || EU-RO-MR by DNV-GL
Device Short Name:
LC1G
Connection Pitch:
70 mm
[Uc] Control Circuit Voltage:
200...500 V AC 50/60 Hz || 200...500 V DC
Connections - Terminals:
power circuit: bar 2 - busbar cross section: 52 x 20 mm || power circuit: lugs-ring terminals 1 185-185 mm² || power circuit: bolted connection || control circuit: push-in 1 0.2-2.5 mm² - cable stiffness: solid stranded without cable end || control
Environmental Disclosure:
ENVPEP2105013
Rated Breaking Capacity:
5550 A at 440 V
China Rohs Regulation:
X
Mechanical Robustness:
vibrations 5-300 Hz 2 gn contactor open || vibrations 5-300 Hz 4 gn contactor closed || shocks 10 gn 11 ms contactor open || shocks 15 gn 11 ms contactor closed
Circularity Profile:
ENVEOLI2105013
Motor Power Kw:
180 kW at 230 V AC 50/60 Hz (AC-3e) || 315 kW at 400 V AC 50/60 Hz (AC-3e) || 335 kW at 415 V AC 50/60 Hz (AC-3e) || 355 kW at 440 V AC 50/60 Hz (AC-3e) || 375 kW at 500 V AC 50/60 Hz (AC-3e) || 500 kW at 690 V AC 50/60 Hz (AC-3e) || 450 kW at 1000 V
Product Or Component Type:
contactor
Range Of Product:
TeSys Giga
Mounting Support:
plate
Maximum Operating Rate:
600 cyc/h AC-3 || 600 cyc/h AC-3e || 300 cyc/h AC-1 || 150 cyc/h AC-4
Contactor Application:
power switching || motor control
Country of Origin:
China
Tightening Torque:
58 N.m
Coil Technology:
built-in bidirectional peak limiting
Height:
284 mm
Ip Degree Of Protection:
IP2X front face with shrouds IEC 60529 || IP2X front face with shrouds VDE 0106
Range:
TeSys
[Ue] Rated Operational Voltage:
<= 1000 V AC 50/60 Hz || <= 460 V DC
Hold-In Power Consumption In Va:
17-17 VA
Operating Time:
40...70 ms closing || 15...50 ms opening
Associated Fuse Rating:
630 A aM at <= 440 V for motor || 500 A aM at <= 690 V for motor || 1250 A gG at <= 690 V
Weight:
14.2 kg
Utilisation Category:
AC-1 || AC-3 || AC-3e || AC-4 || AC-5a || AC-5b || AC-6a || AC-6b || AC-8a || AC-8b || DC-1 || DC-3 || DC-5
Power Dissipation Per Pole:
70 W AC-1 - Ith 1050 A || 26 W AC-3 - Ith 630 A
[Ie] Rated Operational Current:
1050 A (at <40°C) at <= 1000 V AC-1 || 630 A (at <60°C) at <= 440 V AC-3
[Icw] Rated Short-Time Withstand Current:
5.05 kA - 10 s || 4.4 kA - 30 s || 3.4 kA - 1 min || 2.2 kA - 3 min || 1.6 kA - 10 min
Irms Rated Making Capacity:
7220 A at 440 V
Maximum Horse Power Rating:
250 hp at 200/208 V 60 Hz || 300 hp at 230/240 V 60 Hz || 600 hp at 460/480 V 60 Hz || 700 hp at 575/600 V 60 Hz
Auxiliary Contact Composition:
1 NO + 1 NC
Protective Treatment:
TH
Inrush Power In Va:
670-670 VA
Poles Description:
3P
Net Weight:
14.2 kg
Sustainable Offer Status:
Green Premium product
Inrush Power In W:
390 W
Average Impedance:
0.000065 Ohm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Depth:
266 mm
Ambient Air Temperature For Operation:
-25-60°C
Control Circuit Voltage Limits:
operational: 0.8 Uc Min...1.1 Uc Max (at <60°C) || drop-out: 0.1 Uc Max...0.45 Uc Min (at <60°C)
$3,950.00