- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Hold-In Power Consumption In Va:
- 4.5-4.5 VA (at 20°C)
- Sustainable Packaging:
- Yes
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Motor Power Kw:
- 1.5 kW 220...230 V AC 50/60 Hz AC-3 || 2.2 kW 380...415 V AC 50/60 Hz AC-3 || 3 kW 440/690 V AC 50/60 Hz AC-3 || 1.5 kW 220...230 V AC 50/60 Hz AC-3e || 2.2 kW 380...415 V AC 50/60 Hz AC-3e || 3 kW 440/690 V AC 50/60 Hz AC-3e || 1.5 kW 220...230 V AC
- Ip Degree Of Protection:
- IP2X VDE 0106
- Country of Origin:
- Indonesia
- Range:
- TeSys
- Mechanical Robustness:
- shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
- Contactor Application:
- motor control
- Electrical Durability:
- 1.3 Mcycles 6 A AC-3 <= 440 V || 1.3 Mcycles 6 A AC-3e <= 440 V || 0.05 Mcycles 36 A AC-4 <= 440 V
- Reach Free Of Svhc:
- Yes
- Warranty:
- 18 months
- Mercury Free:
- Yes
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- Weight:
- 0.18 kg
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Product Or Component Type:
- contactor
- Depth:
- 57 mm
- Maximum Operating Rate:
- 3600 cyc/h
- Signaling Circuit Frequency:
- <= 400 Hz
- Ambient Air Temperature For Storage:
- -50-80°C
- Auxiliary Contact Composition:
- 1 NC
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Environmental Disclosure:
- ENVPEP1503003EN
- Auxiliary Contacts Type:
- instantaneous 1 NC
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Mounting Support:
- plate || rail
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
- Heat Dissipation:
- 1.3-1.3 W
- Device Application:
- control
- [Ie] Rated Operational Current:
- 6 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 6 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Irms Rated Making Capacity:
- 110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Rohs Exemption Information:
- Yes
- Non Overlap Distance:
- 0.5 mm
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Circularity Profile:
- ENVEOLI1503003EN
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
- Mechanical Durability:
- 10 Mcycles