Schneider Electric LC1K0601P7 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 6A, 1 NC aux., 230VAC coil
Schneider Electric
$57.00
LC1K0601P7 is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 6A AC-3 2.2kW@400V, it includes a 230V 50/60Hz AC coil and 1NC auxiliary contact. LC1K0601P7 is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 2.2kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it includes a 230V 50/60Hz AC coil and 1NC built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Provides a control circuit compatible with 50Hz and 60Hz supplies and 1NC built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
- Contactor Application:
- motor control
- Eu Rohs Directive:
- Compliant
- Reach Free Of Svhc:
- Yes
- Device Short Name:
- LC1K
- Ambient Air Temperature For Storage:
- -50-80°C
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- [Ie] Rated Operational Current:
- 6 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 6 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Rohs Exemption Information:
- Yes
- Weight:
- 0.18 kg
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Depth:
- 57 mm
- Device Application:
- control
- Poles Description:
- 3P
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
- Country of Origin:
- France
- Auxiliary Contacts Type:
- instantaneous 1 NC
- Maximum Operating Rate:
- 3600 cyc/h
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
- Signaling Circuit Frequency:
- <= 400 Hz
- Sustainable Offer Status:
- Green Premium product
- Circularity Profile:
- ENVEOLI1503003EN
- Ip Degree Of Protection:
- IP2X VDE 0106
- Mechanical Robustness:
- shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Auxiliary Contact Composition:
- 1 NC
- Toxic Heavy Metal Free:
- Yes
- Non Overlap Distance:
- 0.5 mm
- Mounting Support:
- plate || rail
- Sustainable Packaging:
- Yes
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
- Net Weight:
- 0.18 kg
- Mercury Free:
- Yes
- Warranty:
- 18 months
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Mechanical Durability:
- 10 Mcycles
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Tightening Torque:
- 0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Overvoltage Category:
- III
- Irms Rated Making Capacity:
- 110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Environmental Disclosure:
- ENVPEP1503003EN
- Range:
- TeSys