Schneider Electric

Schneider Electric LC1K06105F7 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 6A, 1 NO aux., 110VAC coil

(No reviews yet) Write a Review
SKU:
LC1K06105F7
MPN:
LC1K06105F7
Condition:
New
Control Circuit Voltage Limits:
operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Toxic Heavy Metal Free:
Yes
Mounting Support:
printed circuit boards
[Uc] Control Circuit Voltage:
110 V AC 50/60 Hz
Overvoltage Category:
III
Average Impedance:
3 mOhm - Ith 20 A 50 Hz for power circuit
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
Utilisation Category:
AC-3 || AC-3e || AC-4
Mechanical Robustness:
shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Depth:
57 mm
Eu Rohs Directive:
Compliant
[Icw] Rated Short-Time Withstand Current:
90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
Warranty:
18 months
Country of Origin:
Indonesia
Connections - Terminals:
solder pins 0.035 mm)
Product Or Component Type:
contactor
[Ui] Rated Insulation Voltage:
power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
Ambient Air Temperature For Storage:
-50-80°C
Net Weight:
0.18 kg
Hold-In Power Consumption In Va:
4.5-4.5 VA (at 20°C)
Auxiliary Contacts Type:
instantaneous 1 NO
Width:
45 mm
Non Overlap Distance:
0.5 mm
Motor Power Kw:
1.5 kW 220...230 V AC 50/60 Hz AC-3 || 2.2 kW 380...415 V AC 50/60 Hz AC-3 || 3 kW 440/690 V AC 50/60 Hz AC-3 || 1.5 kW 220...230 V AC 50/60 Hz AC-3e || 2.2 kW 380...415 V AC 50/60 Hz AC-3e || 3 kW 440/690 V AC 50/60 Hz AC-3e || 1.5 kW 220...230 V AC
Operating Time:
10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
Maximum Operating Rate:
3600 cyc/h
Ip Degree Of Protection:
IP2X VDE 0106
Rohs Exemption Information:
Yes
Sustainable Offer Status:
Green Premium product
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Pole Contact Composition:
3 NO
Rated Breaking Capacity:
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
Signaling Circuit Frequency:
<= 400 Hz
Height:
58 mm
Reach Free Of Svhc:
Yes
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Device Application:
control
Minimum Switching Current:
5 mA for Signaling circuit
Sustainable Packaging:
Yes
Product Certifications:
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Range:
TeSys
Electrical Durability:
1.3 Mcycles 6 A AC-3 <= 440 V || 1.3 Mcycles 6 A AC-3e <= 440 V || 0.05 Mcycles 36 A AC-4 <= 440 V
Standards:
EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
Mercury Free:
Yes
Mechanical Durability:
10 Mcycles
Control Circuit Type:
AC 50/60 Hz
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
$71.25

Description

TeSys K contactor, 3 poles (3NO), for motor control applications up to 6A/690V AC-3 (2.2kW@400V). It provides a 110V 50/60Hz AC coil, 1NO built-in auxiliary contact, connection by solder pins for printed circuit boards. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
View AllClose