- Control Circuit Type:
- AC 50/60 Hz standard
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Mechanical Durability:
- 10 Mcycles
- Device Short Name:
- LC1K
- Mounting Support:
- rail || plate
- Pole Contact Composition:
- 3 NO
- Poles Description:
- 3P
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Product Or Component Type:
- contactor
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- Associated Fuse Rating:
- 10 A gG for control circuit conforming to IEC 60947 || 10 A gG for control circuit conforming to VDE 0660 || 25 A gG at <= 440 V for power circuit
- Mercury Free:
- Yes
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc at 50/60 Hz (at <50°C) || drop-out: >= 0.20 Uc at 50/60 Hz (at <50°C)
- Utilisation Category:
- AC-3 || AC-3e || AC-4
- Minimum Switching Voltage:
- 17 V for control circuit
- Fire Resistance:
- 850°C IEC 60695-2-1
- Insulation Resistance:
- > 10 MOhm for control circuit
- Warranty:
- 18 months
- Maximum Operating Rate:
- 3600 cyc/h
- Motor Power Kw:
- 1.5 kW 220...230 V AC 50/60 Hz AC-3 || 2.2 kW 380...415 V AC 50/60 Hz AC-3 || 3 kW 440/690 V AC 50/60 Hz AC-3 || 1.5 kW 220...230 V AC 50/60 Hz AC-3e || 2.2 kW 380...415 V AC 50/60 Hz AC-3e || 3 kW 440/690 V AC 50/60 Hz AC-3e || 1.5 kW 220...230 V AC
- Minimum Switching Current:
- 5 mA for control circuit
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Environmental Disclosure:
- ENVPEP1503003EN
- Sustainable Offer Status:
- Green Premium product
- Rohs Exemption Information:
- Yes
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Coil Technology:
- without built-in bidirectional peak limiting diode suppressor
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Reach Free Of Svhc:
- Yes
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
- Weight:
- 0.18 kg
- Country of Origin:
- France
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Net Weight:
- 0.18 kg
- [Ui] Rated Insulation Voltage:
- control circuit 690 V BS 5424 || control circuit 690 V IEC 60947 || power circuit 690 V BS 5424 || power circuit 690 V IEC 60947 || power circuit 690 V NF C 20-040 || control circuit 750 V VDE 0110 group C || power circuit 750 V VDE 0110 group C || c
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Eu Rohs Directive:
- Compliant
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Contactor Application:
- motor control
- Flame Retardance:
- class C2 conforming to NF F 16-101 || class C2 conforming to NF F 16-102 || V1 conforming to UL 94
- Depth:
- 57 mm
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 15...25 ms coil de-energisation and NC opening || 10...20 ms between energisation of coil and closing of NO contact || 5...15 ms coil energisation and NC opening