TeSys K contactor, 3 poles (3NO), for motor control applications up to 6A/690V AC-3 (2.2kW@400V). It provides a 400-415V 50/60Hz AC coil, 1NO built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
- Non Overlap Distance:
- 0.5 mm
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- Signaling Circuit Frequency:
- <= 400 Hz
- Irms Rated Making Capacity:
- 110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Toxic Heavy Metal Free:
- Yes
- Environmental Disclosure:
- ENVPEP1503003EN
- Utilisation Category:
- AC-3 || AC-3e || AC-4
- Hold-In Power Consumption In Va:
- 4.5-4.5 VA (at 20°C)
- Range:
- TeSys
- Mechanical Durability:
- 10 Mcycles
- Heat Dissipation:
- 1.3-1.3 W
- [Uc] Control Circuit Voltage:
- 400...415 V AC 50/60 Hz
- [Ui] Rated Insulation Voltage:
- power circuit 600 V UL 508 || power circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-4-1 || Signaling circuit 690 V IEC 60947-5-1 || Signaling circuit 600 V UL 508 || power circuit 600 V CSA C22.2 No 14 || Signaling circuit 600 V CSA
- Country of Origin:
- Indonesia
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Weight:
- 0.18 kg
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Rohs Exemption Information:
- Yes
- [Ie] Rated Operational Current:
- 6 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 6 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Device Short Name:
- LC1K
- Control Circuit Type:
- AC 50/60 Hz
- Pole Contact Composition:
- 3 NO
- Ip Degree Of Protection:
- IP2X VDE 0106
- Contactor Application:
- motor control
- Warranty:
- 18 months
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- Net Weight:
- 0.18 kg
- Maximum Operating Rate:
- 3600 cyc/h
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Sustainable Packaging:
- Yes
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Device Application:
- control
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Product Or Component Type:
- contactor
- Overvoltage Category:
- III
- Sustainable Offer Status:
- Green Premium product
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Height:
- 58 mm
- Mechanical Robustness:
- shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
- Motor Power Kw:
- 1.5 kW 220...230 V AC 50/60 Hz AC-3 || 2.2 kW 380...415 V AC 50/60 Hz AC-3 || 3 kW 440/690 V AC 50/60 Hz AC-3 || 1.5 kW 220...230 V AC 50/60 Hz AC-3e || 2.2 kW 380...415 V AC 50/60 Hz AC-3e || 3 kW 440/690 V AC 50/60 Hz AC-3e || 1.5 kW 220...230 V AC
- Eu Rohs Directive:
- Compliant
- Tightening Torque: