Schneider Electric

Schneider Electric LC1K0910F7 Contactor, IEC, TeSys K, 9A, 3 P, 5 HP at 480VAC, nonreversing, 1 NO auxilliary contact, 110VAC 50/60 Hz coil

(No reviews yet) Write a Review
SKU:
LC1K0910F7
MPN:
LC1K0910F7
Condition:
New
Insulation Resistance:
> 10 MOhm for Signaling circuit
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Operating Altitude:
6561.68 ft (2000 m) without derating
Reach Free Of Svhc:
Yes
Auxiliary Contacts Type:
instantaneous 1 NO
Product Or Component Type:
contactor
Average Impedance:
3 mOhm - Ith 20 A 50 Hz for power circuit
Range:
TeSys
Device Short Name:
LC1K
Country of Origin:
France
Signaling Circuit Frequency:
<= 400 Hz
[Uc] Control Circuit Voltage:
110 V AC 50/60 Hz
Warranty:
18 months
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
[Ith] Conventional Free Air Thermal Current:
20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
Electrical Durability:
1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
Minimum Switching Voltage:
17 V for Signaling circuit
Depth:
57 mm
Rated Breaking Capacity:
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
Irms Rated Making Capacity:
110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
Contactor Application:
resistive load || motor control
Sustainable Packaging:
Yes
Product Certifications:
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Poles Description:
3P
[Icw] Rated Short-Time Withstand Current:
90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
Height:
58 mm
Environmental Disclosure:
ENVPEP1503003EN
Heat Dissipation:
1.3-1.3 W
Control Circuit Type:
AC 50/60 Hz
Control Circuit Voltage Limits:
operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
Motor Power Kw:
2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440/690 V AC 50/60 Hz AC-3 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440/690 V AC 50/60 Hz AC-3e || 2.2 kW 220...230 V AC 50/
Eu Rohs Directive:
Compliant
Hold-In Power Consumption In Va:
4.5-4.5 VA (at 20°C)
Standards:
EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
Auxiliary Contact Composition:
1 NO
Operating Time:
10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
Inrush Power In Va:
30-30 VA (at 20°C)
Circularity Profile:
ENVEOLI1503003EN
Device Application:
control
Mechanical Robustness:
shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
Connections - Terminals:
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
Minimum Switching Current:
5 mA for Signaling circuit
$75.00

Description

TeSys K contactors have been designed for perfect integration into control systems. They can be used to create motor starters for any type of application. They can be used to create motor starters for almost any type of application. TeSys K contactors offer quick simple setup, while maintaining a compact size. Contactors have both Horsepower and Kw motor rating for international acceptance. An extennsive line of accessories makes it easy to meet the requirements of most applications. These contactors are UL Listed and CSA certified. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
View AllClose