Schneider Electric

Schneider Electric LC1K0910G7 Contactor, IEC, TeSys K, 9A, 3 P, 5 HP at 480VAC, nonreversing, 1 NO auxilliary contact, 120VAC 50/60 Hz coil

(No reviews yet) Write a Review
SKU:
LC1K0910G7
MPN:
LC1K0910G7
Condition:
New
Heat Dissipation:
1.3-1.3 W
Rated Breaking Capacity:
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
Eu Rohs Directive:
Compliant
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Overvoltage Category:
III
Mercury Free:
Yes
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Auxiliary Contacts Type:
instantaneous 1 NO
Minimum Switching Current:
5 mA for Signaling circuit
[Icw] Rated Short-Time Withstand Current:
90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
Standards:
EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
Average Impedance:
3 mOhm - Ith 20 A 50 Hz for power circuit
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
Minimum Switching Voltage:
17 V for Signaling circuit
Poles Description:
3P
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
Depth:
57 mm
Range:
TeSys
Control Circuit Voltage Limits:
operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
Hold-In Power Consumption In Va:
4.5-4.5 VA (at 20°C)
Sustainable Packaging:
Yes
Device Application:
control
Toxic Heavy Metal Free:
Yes
Connections - Terminals:
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
Operating Time:
10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
Sustainable Offer Status:
Green Premium product
Utilisation Category:
AC-3 || AC-3e || AC-1 || AC-4
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Electrical Durability:
1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
Control Circuit Type:
AC 50/60 Hz
Product Or Component Type:
contactor
Circularity Profile:
ENVEOLI1503003EN
Insulation Resistance:
> 10 MOhm for Signaling circuit
Irms Rated Making Capacity:
110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
Inrush Power In Va:
30-30 VA (at 20°C)
Device Short Name:
LC1K
Contactor Application:
motor control || resistive load
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Warranty:
18 months
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Signaling Circuit Frequency:
<= 400 Hz
Country of Origin:
United States
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Height:
58 mm
Motor Power Kw:
2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440/690 V AC 50/60 Hz AC-3 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440/690 V AC 50/60 Hz AC-3e || 2.2 kW 220...230 V AC 50/
$75.00

Description

TeSys K contactors have been designed for perfect integration into control systems. They can be used to create motor starters for any type of application. They can be used to create motor starters for almost any type of application. TeSys K contactors offer quick simple setup, while maintaining a compact size. Contactors have both Horsepower and Kw motor rating for international acceptance. An extennsive line of accessories makes it easy to meet the requirements of most applications. These contactors are UL Listed and CSA certified. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
View AllClose