Schneider Electric LC1K0910M72 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 9A, 1 NO aux., 220 to 230VAC coil
Schneider Electric
$85.00
TeSys K contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V), and for non-inductive load control applications up to 20A/690V AC-1. It provides a 220V 50/60Hz AC coil with transient suppressor module, 1NO built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Warranty:
- 18 months
- Device Application:
- control
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Sustainable Offer Status:
- Green Premium product
- Country of Origin:
- France
- Product Or Component Type:
- contactor
- Auxiliary Contact Composition:
- 1 NO
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Hold-In Power Consumption In Va:
- 4.5-4.5 VA (at 20°C)
- Control Circuit Type:
- AC 50/60 Hz
- [Ie] Rated Operational Current:
- 9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Eu Rohs Directive:
- Compliant
- Standards:
- EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Heat Dissipation:
- 1.3-1.3 W
- Poles Description:
- 3P
- Electrical Durability:
- 1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- Range:
- TeSys
- Environmental Disclosure:
- ENVPEP1503003EN
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Sustainable Packaging:
- Yes
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Mechanical Durability:
- 10 Mcycles
- Contactor Application:
- resistive load || motor control
- Overvoltage Category:
- III
- Toxic Heavy Metal Free:
- Yes
- Motor Power Kw:
- 2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440/690 V AC 50/60 Hz AC-3 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440/690 V AC 50/60 Hz AC-3e || 2.2 kW 220...230 V AC 50/
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
- Mercury Free:
- Yes
- Signaling Circuit Frequency:
- <= 400 Hz
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Maximum Operating Rate:
- 3600 cyc/h
- Depth:
- 57 mm
- Reach Free Of Svhc:
- Yes
- Irms Rated Making Capacity:
- 110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
- Rated Breaking Capacity:
- 110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- [Icw] Rated Short-Time Withstand Current:
- 90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
- Utilisation Category:
- AC-3 || AC-3e || AC-1 || AC-4
- Circularity Profile:
- ENVEOLI1503003EN