Schneider Electric

Schneider Electric LC1K0910M72 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 9A, 1 NO aux., 220 to 230VAC coil

(No reviews yet) Write a Review
SKU:
LC1K0910M72
MPN:
LC1K0910M72
Condition:
New
Minimum Switching Voltage:
17 V for Signaling circuit
Warranty:
18 months
Device Application:
control
Operating Altitude:
6561.68 ft (2000 m) without derating
Minimum Switching Current:
5 mA for Signaling circuit
Sustainable Offer Status:
Green Premium product
Country of Origin:
France
Product Or Component Type:
contactor
Auxiliary Contact Composition:
1 NO
Product Certifications:
CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
Hold-In Power Consumption In Va:
4.5-4.5 VA (at 20°C)
Control Circuit Type:
AC 50/60 Hz
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 9 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
Operating Time:
10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Eu Rohs Directive:
Compliant
Standards:
EN/IEC 60947-4-1 || GB/T 14048.4 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Heat Dissipation:
1.3-1.3 W
Poles Description:
3P
Electrical Durability:
1.3 Mcycles 9 A AC-3 <= 440 V || 1.3 Mcycles 9 A AC-3e <= 440 V || 0.16 Mcycles 20 A AC-1 <= 690 V || 0.02 Mcycles 54 A AC-4 <= 440 V
Inrush Power In Va:
30-30 VA (at 20°C)
Range:
TeSys
Environmental Disclosure:
ENVPEP1503003EN
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Sustainable Packaging:
Yes
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical Durability:
10 Mcycles
Contactor Application:
resistive load || motor control
Overvoltage Category:
III
Toxic Heavy Metal Free:
Yes
Motor Power Kw:
2.2 kW 220...230 V AC 50/60 Hz AC-3 || 4 kW 380...415 V AC 50/60 Hz AC-3 || 4 kW 440/690 V AC 50/60 Hz AC-3 || 2.2 kW 220...230 V AC 50/60 Hz AC-3e || 4 kW 380...415 V AC 50/60 Hz AC-3e || 4 kW 440/690 V AC 50/60 Hz AC-3e || 2.2 kW 220...230 V AC 50/
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Control Circuit Voltage Limits:
operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
Mercury Free:
Yes
Signaling Circuit Frequency:
<= 400 Hz
Average Impedance:
3 mOhm - Ith 20 A 50 Hz for power circuit
Maximum Operating Rate:
3600 cyc/h
Depth:
57 mm
Reach Free Of Svhc:
Yes
Irms Rated Making Capacity:
110 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
Rated Breaking Capacity:
110 A at 220...230 V conforming to IEC 60947 || 110 A at 380...400 V conforming to IEC 60947 || 110 A at 415 V conforming to IEC 60947 || 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conformin
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
[Icw] Rated Short-Time Withstand Current:
90 A 50°C - 1 s for power circuit || 85 A 50°C - 5 s for power circuit || 80 A 50°C - 10 s for power circuit || 60 A 50°C - 30 s for power circuit || 45 A 50°C - 1 min for power circuit || 40 A 50°C - 3 min for power circuit || 20 A 50°C - >= 15 min
Utilisation Category:
AC-3 || AC-3e || AC-1 || AC-4
Circularity Profile:
ENVEOLI1503003EN
$85.00

Description

TeSys K contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V), and for non-inductive load control applications up to 20A/690V AC-1. It provides a 220V 50/60Hz AC coil with transient suppressor module, 1NO built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
View AllClose