Schneider Electric LC1K1210L7 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 12 A, 1 NO aux., 200 to 208VAC coil
Schneider Electric
$86.00
TeSys K contactor, 3 poles (3NO), for motor control applications up to 12A/690V AC-3 (5.5kW@400V), and for non-inductive load control applications up to 20A/690V AC-1. It provides a 200-208V 50/60Hz AC coil, 1NO built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
- Maximum Operating Rate:
- 3600 cyc/h
- Mounting Support:
- plate || rail
- Utilisation Category:
- AC-3 || AC-3e || AC-1 || AC-4
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Environmental Disclosure:
- ENVPEP1503003EN
- Hold-In Power Consumption In Va:
- 4.5-4.5 VA (at 20°C)
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Auxiliary Contact Composition:
- 1 NO
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Device Application:
- control
- [Icw] Rated Short-Time Withstand Current:
- 115 A 50°C - 1 s for power circuit || 105 A 50°C - 5 s for power circuit || 100 A 50°C - 10 s for power circuit || 75 A 50°C - 30 s for power circuit || 55 A 50°C - 1 min for power circuit || 50 A 50°C - 3 min for power circuit || 25 A 50°C - >= 15 m
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Depth:
- 57 mm
- Product Or Component Type:
- contactor
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Height:
- 58 mm
- Control Circuit Type:
- AC 50/60 Hz
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
- Mercury Free:
- Yes
- Sustainable Packaging:
- Yes
- Motor Power Kw:
- 3 kW 220...230 V AC 50/60 Hz AC-3 || 5.5 kW 380...415 V AC 50/60 Hz AC-3 || 5.5 kW 440 V AC 50/60 Hz AC-3 || 4 kW 690 V AC 50/60 Hz AC-3 || 3 kW 220...230 V AC 50/60 Hz AC-3e || 5.5 kW 380...415 V AC 50/60 Hz AC-3e || 5.5 kW 440 V AC 50/60 Hz AC-3e |
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Ip Degree Of Protection:
- IP2X VDE 0106
- Poles Description:
- 3P
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Signaling Circuit Frequency:
- <= 400 Hz
- Mechanical Robustness:
- shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
- Reach Free Of Svhc:
- Yes
- [Uc] Control Circuit Voltage:
- 200...208 V AC 50/60 Hz
- Eu Rohs Directive:
- Compliant
- Rohs Exemption Information:
- Yes
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Contactor Application:
- motor control || resistive load
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Country of Origin:
- France
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- Ambient Air Temperature For Storage:
- -50-80°C
- Overvoltage Category:
- III
- [Ie] Rated Operational Current:
- 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Sustainable Offer Status:
- Green Premium product
- Rated Breaking Capacity:
- 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
- Toxic Heavy Metal Free:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102