Maximum Operating Rate:
3600 cyc/h
Mounting Support:
plate || rail
Utilisation Category:
AC-3 || AC-3e || AC-1 || AC-4
Protective Treatment:
TC IEC 60068 || TC DIN 50016
Environmental Disclosure:
ENVPEP1503003EN
Hold-In Power Consumption In Va:
4.5-4.5 VA (at 20°C)
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
Auxiliary Contact Composition:
1 NO
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Device Application:
control
[Icw] Rated Short-Time Withstand Current:
115 A 50°C - 1 s for power circuit || 105 A 50°C - 5 s for power circuit || 100 A 50°C - 10 s for power circuit || 75 A 50°C - 30 s for power circuit || 55 A 50°C - 1 min for power circuit || 50 A 50°C - 3 min for power circuit || 25 A 50°C - >= 15 m
Connections - Terminals:
screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
Minimum Switching Voltage:
17 V for Signaling circuit
Depth:
57 mm
Product Or Component Type:
contactor
Operating Altitude:
6561.68 ft (2000 m) without derating
Height:
58 mm
Control Circuit Type:
AC 50/60 Hz
Operating Time:
10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
Mercury Free:
Yes
Sustainable Packaging:
Yes
Motor Power Kw:
3 kW 220...230 V AC 50/60 Hz AC-3 || 5.5 kW 380...415 V AC 50/60 Hz AC-3 || 5.5 kW 440 V AC 50/60 Hz AC-3 || 4 kW 690 V AC 50/60 Hz AC-3 || 3 kW 220...230 V AC 50/60 Hz AC-3e || 5.5 kW 380...415 V AC 50/60 Hz AC-3e || 5.5 kW 440 V AC 50/60 Hz AC-3e |
Minimum Switching Current:
5 mA for Signaling circuit
Ip Degree Of Protection:
IP2X VDE 0106
Poles Description:
3P
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Signaling Circuit Frequency:
<= 400 Hz
Mechanical Robustness:
shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 || shocks contactor opened, on X axis6 Gn for 11
Reach Free Of Svhc:
Yes
[Uc] Control Circuit Voltage:
200...208 V AC 50/60 Hz
Eu Rohs Directive:
Compliant
Rohs Exemption Information:
Yes
Control Circuit Voltage Limits:
operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Contactor Application:
motor control || resistive load
Insulation Resistance:
> 10 MOhm for Signaling circuit
Country of Origin:
France
Associated Fuse Rating:
25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
Ambient Air Temperature For Storage:
-50-80°C
Overvoltage Category:
III
[Ie] Rated Operational Current:
12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
Reach Regulation:
Free of Substances of Very High Concern above the threshold
Sustainable Offer Status:
Green Premium product
Rated Breaking Capacity:
110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
Toxic Heavy Metal Free:
Yes
[Uimp] Rated Impulse Withstand Voltage:
8 kV
Flame Retardance:
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
$86.00

Description

TeSys K contactor, 3 poles (3NO), for motor control applications up to 12A/690V AC-3 (5.5kW@400V), and for non-inductive load control applications up to 20A/690V AC-1. It provides a 200-208V 50/60Hz AC coil, 1NO built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).