Schneider Electric LC1K1210U7 Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 12 A, 1 NO aux., 230 to 240VAC coil
Schneider Electric
$86.00
LC1K1210U7 is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 12A AC-3 5.5kW@400V, it includes a 240V 50/60Hz AC coil and 1NO auxiliary contact. LC1K1210U7 is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 5.5kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it includes a 240V 50/60Hz AC coil and 1NO built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Provides a control circuit compatible with 50Hz and 60Hz supplies and 1NO built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
- Average Impedance:
- 3 mOhm - Ith 20 A 50 Hz for power circuit
- Connections - Terminals:
- screw clamp terminals 1 1.5-4 mm²solid || screw clamp terminals 1 0.75-4 mm²flexible without cable end || screw clamp terminals 1 0.34-2.5 mm²flexible with cable end || screw clamp terminals 2 1.5-4 mm²solid || screw clamp terminals 2 0.75-4
- Motor Power Kw:
- 3 kW 220...230 V AC 50/60 Hz AC-3 || 5.5 kW 380...415 V AC 50/60 Hz AC-3 || 5.5 kW 440 V AC 50/60 Hz AC-3 || 4 kW 690 V AC 50/60 Hz AC-3 || 3 kW 220...230 V AC 50/60 Hz AC-3e || 5.5 kW 380...415 V AC 50/60 Hz AC-3e || 5.5 kW 440 V AC 50/60 Hz AC-3e |
- Poles Description:
- 3P
- Control Circuit Type:
- AC 50/60 Hz
- Device Short Name:
- LC1K
- Protective Treatment:
- TC IEC 60068 || TC DIN 50016
- Toxic Heavy Metal Free:
- Yes
- Tightening Torque:
- 0.8-1.3 N.m screw clamp terminals Philips No 2 || 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm || 0.8-1.3 N.m screw clamp terminals pozidriv No 2
- Irms Rated Making Capacity:
- 144 A AC for power circuit conforming to IEC 60947 || 110 A AC for Signaling circuit conforming to IEC 60947
- Net Weight:
- 0.18 kg
- Control Circuit Voltage Limits:
- operational: 0.8...1.15 Uc (at <50°C) || drop-out: >= 0.20 Uc (at <50°C)
- Width:
- 45 mm
- Contactor Application:
- motor control || resistive load
- Product Or Component Type:
- contactor
- Reach Free Of Svhc:
- Yes
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Overvoltage Category:
- III
- Auxiliary Contacts Type:
- instantaneous 1 NO
- Hold-In Power Consumption In Va:
- 4.5-4.5 VA (at 20°C)
- Environmental Disclosure:
- ENVPEP1503003EN
- Mercury Free:
- Yes
- Rated Breaking Capacity:
- 110 A at 440 V conforming to IEC 60947 || 80 A at 500 V conforming to IEC 60947 || 70 A at 660...690 V conforming to IEC 60947
- [Icw] Rated Short-Time Withstand Current:
- 115 A 50°C - 1 s for power circuit || 105 A 50°C - 5 s for power circuit || 100 A 50°C - 10 s for power circuit || 75 A 50°C - 30 s for power circuit || 55 A 50°C - 1 min for power circuit || 50 A 50°C - 3 min for power circuit || 25 A 50°C - >= 15 m
- Mounting Support:
- rail || plate
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Operating Time:
- 10...20 ms coil de-energisation and NO opening || 10...20 ms coil energisation and NO closing
- Auxiliary Contact Composition:
- 1 NO
- Non Overlap Distance:
- 0.5 mm
- Country of Origin:
- Indonesia
- Inrush Power In Va:
- 30-30 VA (at 20°C)
- [Ie] Rated Operational Current:
- 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit || 20 A (at <60°C) at <= 690 V AC AC-1 for power circuit
- Maximum Operating Rate:
- 3600 cyc/h
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Device Application:
- control
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC <= 400 Hz || Signaling circuit <= 690 V AC <= 400 Hz
- Sustainable Offer Status:
- Green Premium product
- Range:
- TeSys
- Associated Fuse Rating:
- 25 A gG at <= 440 V for power circuit || 25 A aM for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947 || 10 A gG for Signaling circuit conforming to VDE 0660
- [Ith] Conventional Free Air Thermal Current:
- 20 A (at 60°C) for power circuit || 10 A (at 50°C) for Signaling circuit
- Flame Retardance:
- V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
- Operating Altitude:
- 6561.68 ft (2000 m) without derating
- Product Certifications:
- CB Scheme || CCC || UL || CSA || EAC || CE || UKCA
- Signaling Circuit Frequency:
- <= 400 Hz