- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- Contactor Application:
- resistive load || motor control
- Electrical Durability:
- 0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V
- [Uc] Control Circuit Voltage:
- 24 V DC
- Control Circuit Voltage Limits:
- 0.1...0.25 Uc -40-70°C drop-out DC || 0.7...1.25 Uc -40-60°C operational DC || 1...1.25 Uc 60-70°C operational DC
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Inrush Power In W:
- 5.4-5.4 W 20°C)
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- [Ie] Rated Operational Current:
- 9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 16 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Poles Description:
- 3P
- Signaling Circuit Frequency:
- 25...400 Hz
- Device Presentation:
- preassembled with reversing power busbar
- Rohs Exemption Information:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Warranty:
- 18 months
- Country of Origin:
- United States
- Average Impedance:
- 2.5 mOhm - Ith 16 A 50 Hz for power circuit
- Device Short Name:
- LC2D
- Circularity Profile:
- ENVEOLI1102030EN
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Motor Power Kw:
- 2.2 kW at 220...230 V AC 50 Hz || 4 kW at 380...400 V AC 50 Hz || 4 kW at 415...440 V AC 50 Hz || 5.5 kW at 500 V AC 50 Hz || 5.5 kW at 660...690 V AC 50 Hz
- Pvc Free:
- Yes
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Control Circuit Type:
- DC standard
- Operating Time:
- 53.55...72.45 ms closing || 16...24 ms opening
- Range:
- TeSys || TeSys Deca
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Weight:
- 1.017 kg
- Pollution Degree:
- 3
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pole Contact Composition:
- 3 NO
- [Ith] Conventional Free Air Thermal Current:
- 16 A (at 60°C) for power circuit || 10 A (at 60°C) for Signaling circuit
- Protective Cover:
- with
- Product Or Component Type:
- reversing contactor
- Associated Fuse Rating:
- 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947-5-1
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Fire Resistance:
- 850°C IEC 60695-2-1
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
- Width:
- 90 mm
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Mercury Free:
- Yes
- Utilisation Category:
- AC-1 || AC-3