- Product Name:
- TeSys D || TeSys Deca
- Net Weight:
- 1.017 kg
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Circularity Profile:
- ENVEOLI1102030EN
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Product Certifications:
- DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
- Poles Description:
- 3P
- [Icw] Rated Short-Time Withstand Current:
- 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Pole Contact Composition:
- 3 NO
- Range:
- TeSys || TeSys Deca
- Device Presentation:
- preassembled with reversing power busbar
- Rohs Exemption Information:
- Yes
- Interlocking Type:
- mechanical
- Protective Cover:
- with
- Fire Resistance:
- 850°C IEC 60695-2-1
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Irms Rated Making Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
- Operating Time:
- 65.45...88.55 ms closing || 20...30 ms opening
- Mounting Support:
- plate || rail
- Coil Technology:
- built-in bidirectional peak limiting diode suppressor
- Height:
- 99 mm
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- [Uc] Control Circuit Voltage:
- 24 V DC
- Eu Rohs Directive:
- Compliant with Exemptions
- Signaling Circuit Frequency:
- 25...400 Hz
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Protective Treatment:
- TH IEC 60068-2-30
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Utilisation Category:
- AC-1 || AC-3 || AC-3e
- Environmental Disclosure:
- ENVPEP110230EN
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- Associated Fuse Rating:
- 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947-5-1
- Overvoltage Category:
- III
- Width:
- 90 mm
- Inrush Power In W:
- 2.4-2.4 W 20°C)
- Mercury Free:
- Yes
- Connections - Terminals:
- power circuit spring terminals 1 2.5-2.5 mm²flexible without cable end || power circuit spring terminals 2 2.5-2.5 mm²flexible without cable end || control circuit spring terminals 1 2.5-2.5 mm²flexible without cable end || control circuit spring
- Flame Retardance:
- V1 conforming to UL 94
- Hold-In Power Consumption In W:
- 2.4-2.4 W 20°C
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Country of Origin:
- France
- Motor Power Kw:
- 2.2 kW at 220...230 V AC 50-60 Hz || 4 kW at 380...400 V AC 50-60 Hz || 4 kW at 415 V AC 50-60 Hz || 4 kW at 440 V AC 50-60 Hz || 5.5 kW at 500 V AC 50-60 Hz || 5.5 kW at 660...690 V AC 50-60 Hz
- Power Dissipation Per Pole:
- 0.2 W AC-3 || 1.56 W AC-1 || 0.2 W AC-3e
- Sustainable Offer Status:
- Green Premium product
- Product Or Component Type:
- reversing contactor
- Device Short Name:
- LC2D