- Circularity Profile:
- ENVEOLI1501004
- Connections - Terminals:
- power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp
- Product Name:
- TeSys D || TeSys Deca
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Poles Description:
- 3P
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- [Icw] Rated Short-Time Withstand Current:
- 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Width:
- 90 mm
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Toxic Heavy Metal Free:
- Yes
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Eu Rohs Directive:
- Compliant
- Range:
- TeSys || TeSys Deca
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Signaling Circuit Frequency:
- 25...400 Hz
- Mercury Free:
- Yes
- Net Weight:
- 0.687 kg
- Contactor Application:
- resistive load || motor control
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Device Short Name:
- LC2D
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Depth:
- 86 mm
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Fire Resistance:
- 850°C IEC 60695-2-1
- Power Dissipation Per Pole:
- 0.2 W AC-3 || 1.56 W AC-1 || 0.2 W AC-3e
- Mounting Support:
- rail || plate
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Control Circuit Type:
- AC 50/60 Hz
- Product Certifications:
- DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Product Or Component Type:
- reversing contactor
- [Ie] Rated Operational Current:
- 9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Heat Dissipation:
- 2-3 W 50/60 Hz
- Overvoltage Category:
- III
- Tightening Torque:
- power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
- Maximum Horse Power Rating:
- 0.5 hp at 115 V AC 60 Hz for 1 phase motors || 1 hp at 230/240 V AC 60 Hz for 1 phase motors || 2 hp at 200/208 V AC 60 Hz for 3 phase motors || 2 hp at 230/240 V AC 60 Hz for 3 phase motors || 5 hp at 460/480 V AC 60 Hz for 3 phase motors || 7.5 hp
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
- Flame Retardance:
- V1 conforming to UL 94