Schneider Electric

Schneider Electric LC2D09G7V IEC contactor, TeSys Deca reversing, 9A, 5HP at 480VAC, 3 phase, 3P, 3NO, 120VAC 50/60Hz coil, open style

(No reviews yet) Write a Review
SKU:
LC2D09G7V
MPN:
LC2D09G7V
Condition:
New
Pvc Free:
Yes
Electrical Durability:
0.6 Mcycles 25 A AC-1 <= 440 V || 2 Mcycles 9 A AC-3 <= 440 V
Protective Cover:
with
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Product Or Component Type:
reversing contactor
Environmental Disclosure:
ENVPEP1501004
Coil Technology:
without built-in suppressor module
Utilisation Category:
AC-3 || AC-1
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
[Ie] Rated Operational Current:
9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Overvoltage Category:
III
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
Climatic Withstand:
IACS E10 || IEC 60947-1 Annex Q category D
Ip Degree Of Protection:
IP20 front face IEC 60529
Rated Breaking Capacity:
250 A at 440 V for power circuit conforming to IEC 60947
Country of Origin:
United States
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Signaling Circuit Frequency:
25...400 Hz
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Maximum Operating Rate:
3600 cyc/h 60°C
Operating Time:
12...22 ms closing || 4...19 ms opening
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current:
5 mA for Signaling circuit
Interlocking Type:
electrical and mechanical
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Power Dissipation Per Pole:
0.2 W AC-3 || 1.56 W AC-1
Eu Rohs Directive:
Compliant
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
Ambient Air Temperature For Storage:
-60-80°C
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Toxic Heavy Metal Free:
Yes
Rohs Exemption Information:
Yes
Warranty:
18 months
Product Certifications:
DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
Pollution Degree:
3
Pole Contact Composition:
3 NO
Mercury Free:
Yes
[Icw] Rated Short-Time Withstand Current:
30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
Heat Dissipation:
2-3 W 50/60 Hz
Protective Treatment:
TH IEC 60068-2-30
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Maximum Horse Power Rating:
0.5 hp at 115 V AC 60 Hz for 1 phase motors || 1 hp at 230/240 V AC 60 Hz for 1 phase motors || 2 hp at 200/208 V AC 60 Hz for 3 phase motors || 2 hp at 230/240 V AC 60 Hz for 3 phase motors || 5 hp at 460/480 V AC 60 Hz for 3 phase motors || 7.5 hp
$293.64

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A reversing inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 2HP at 200 to 208VAC, 2HP at 240VAC, 5HP at 480VAC and 7.5HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 1HP at 240VAC single phase. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Pressure wire connectors are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 3.54 inches wide and 3.39 inches deep. It weighs 1.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
View AllClose