- Protective Treatment:
- TH IEC 60068-2-30
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Contactor Application:
- resistive load || motor control
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Mercury Free:
- Yes
- Maximum Horse Power Rating:
- 0.5 hp at 115 V AC 60 Hz for 1 phase motors || 1 hp at 230/240 V AC 60 Hz for 1 phase motors || 2 hp at 200/208 V AC 60 Hz for 3 phase motors || 2 hp at 230/240 V AC 60 Hz for 3 phase motors || 5 hp at 460/480 V AC 60 Hz for 3 phase motors || 7.5 hp
- Country of Origin:
- France
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Fire Resistance:
- 850°C IEC 60695-2-1
- Associated Fuse Rating:
- 25 A gG at <= 690 V coordination type 1 for power circuit || 20 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for Signaling circuit conforming to IEC 60947-5-1
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Protective Cover:
- with
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Range:
- TeSys || TeSys Deca
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Ambient Air Temperature For Storage:
- -60-80°C
- Device Presentation:
- preassembled with reversing power busbar
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- Pole Contact Composition:
- 3 NO
- Environmental Disclosure:
- ENVPEP110230EN
- Overvoltage Category:
- III
- Rohs Exemption Information:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Connections - Terminals:
- power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp
- Tightening Torque:
- power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
- Warranty:
- 18 months
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- Flame Retardance:
- V1 conforming to UL 94
- Pvc Free:
- Yes
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Pollution Degree:
- 3
- Product Certifications:
- DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
- Power Dissipation Per Pole:
- 0.2 W AC-3 || 1.56 W AC-1
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Signaling Circuit Frequency:
- 25...400 Hz
- Circularity Profile:
- ENVEOLI1102030EN
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Device Short Name:
- LC2D
- Eu Rohs Directive:
- Compliant with Exemptions
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Mechanical Durability:
- 30 Mcycles
- Inrush Power In W:
- 2.4-2.4 W 20°C)
- [Uc] Control Circuit Voltage:
- 12 V DC