- Device Short Name:
- LC2D
- Product Name:
- TeSys Deca
- Mounting Support:
- rail || plate
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
- Average Impedance:
- 2.5 mOhm - Ith 25 A 50 Hz for power circuit
- Device Presentation:
- preassembled with reversing power busbar
- Eu Rohs Directive:
- Compliant
- Rohs Exemption Information:
- Yes
- Pollution Degree:
- 3
- Coil Technology:
- without built-in suppressor module
- Height:
- 77 mm
- Product Or Component Type:
- reversing contactor
- Maximum Horse Power Rating:
- 0.5 hp at 115 V AC 60 Hz for 1 phase motors || 1 hp at 230/240 V AC 60 Hz for 1 phase motors || 2 hp at 200/208 V AC 60 Hz for 3 phase motors || 2 hp at 230/240 V AC 60 Hz for 3 phase motors || 5 hp at 460/480 V AC 60 Hz for 3 phase motors || 7.5 hp
- Pole Contact Composition:
- 3 NO
- Irms Rated Making Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
- Contactor Application:
- resistive load || motor control
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- [Ie] Rated Operational Current:
- 9 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Mercury Free:
- Yes
- Protective Cover:
- with
- Weight:
- 0.687 kg
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Range:
- TeSys || TeSys Deca
- Ambient Air Temperature For Storage:
- -60-80°C
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Flame Retardance:
- V1 conforming to UL 94
- [Icw] Rated Short-Time Withstand Current:
- 30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- Country of Origin:
- United States
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pvc Free:
- Yes
- Utilisation Category:
- AC-3 || AC-1 || AC-3e
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Motor Power Kw:
- 2.2 kW at 220...230 V AC 50-60 Hz || 4 kW at 380...400 V AC 50-60 Hz || 4 kW at 415 V AC 50-60 Hz || 4 kW at 440 V AC 50-60 Hz || 5.5 kW at 500 V AC 50-60 Hz || 5.5 kW at 660...690 V AC 50-60 Hz
- Toxic Heavy Metal Free:
- Yes
- Width:
- 90 mm
- Depth:
- 86 mm
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Warranty:
- 18 months
- Protective Treatment:
- TH IEC 60068-2-30
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Connections - Terminals:
- power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Minimum Switching Voltage:
- 17 V for Signaling circuit