Schneider Electric LC2D1156F7 REVERSING CONTACTOR
Schneider Electric
$1,221.50
REVERSING CONTACTOR
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Rated Breaking Capacity:
- 1100 A at 440 V for power circuit conforming to IEC 60947
- Environmental Disclosure:
- ENVPEP060301EN
- [Ui] Rated Insulation Voltage:
- power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL || power circuit 1000 V IEC 60947-4-1
- Ambient Air Temperature For Storage:
- -60-80°C
- Signaling Circuit Frequency:
- 25...400 Hz
- Climatic Withstand:
- IACS E10
- Fire Resistance:
- 850°C IEC 60695-2-1
- Motor Power Kw:
- 30 kW at 220...230 V AC 50-60 Hz || 55 kW at 380...400 V AC 50-60 Hz || 59 kW at 415 V AC 50-60 Hz || 59 kW at 440 V AC 50-60 Hz || 75 kW at 500 V AC 50-60 Hz || 80 kW at 660...690 V AC 50-60 Hz || 65 kW at 1000 V AC 50-60 Hz
- Warranty:
- 18 months
- Height:
- 158 mm
- [Ie] Rated Operational Current:
- 200 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 115 A (at <60°C) at <= 440 V AC AC-3 for power circuit
- Product Name:
- TeSys Deca
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1260 A at 440 V for power circuit conforming to IEC 60947
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Average Impedance:
- 0.6 mOhm - Ith 200 A 50 Hz for power circuit
- Control Circuit Type:
- AC 50/60 Hz
- Power Dissipation Per Pole:
- 24 W AC-1 || 7.9 W AC-3
- Maximum Operating Rate:
- 2400 cyc/h 60°C
- Depth:
- 148 mm
- Country of Origin:
- Czechia
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Hold-In Power Consumption In Va:
- 2-18 VA 20°C) 0.3 60 Hz || 2-18 VA 20°C) 0.3 50 Hz
- Overvoltage Category:
- III
- Flame Retardance:
- V1 conforming to UL 94
- Electrical Durability:
- 0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V
- Mechanical Durability:
- 8000000 cycles
- Protective Treatment:
- TH IEC 60068-2-30
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Device Short Name:
- LC2D
- [Ith] Conventional Free Air Thermal Current:
- 200 A (at 60°C) for power circuit
- Net Weight:
- 6.35 kg
- Control Circuit Voltage Limits:
- 0.3...0.5 Uc 55-55°C drop-out AC 50/60 Hz || 0.8...1.15 Uc 55-55°C operational AC 50/60 Hz
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Pollution Degree:
- 3
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Product Or Component Type:
- reversing contactor
- Rohs Exemption Information:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Weight:
- 6.35 kg
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947
- Operating Time:
- 20...50 ms closing || 6...20 ms opening
- Heat Dissipation:
- 3-8 W 50/60 Hz
- Inrush Power In Va:
- 280-350 VA 60 Hz 0.8 20°C) || 280-350 VA 50 Hz 0.8 20°C)
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Pvc Free:
- Yes
- Minimum Switching Voltage:
- 17 V for Signaling circuit