Schneider Electric

Schneider Electric LC2D115FE7 TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 115 A - 115 V AC coil

(No reviews yet) Write a Review
SKU:
LC2D115FE7
MPN:
LC2D115FE7
Condition:
New
Minimum Switching Current:
5 mA for Signaling circuit
Width:
266 mm
Rohs Exemption Information:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ue] Rated Operational Voltage:
power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open6 Gn for 11 ms
Flame Retardance:
V1 conforming to UL 94
Fire Resistance:
850°C IEC 60695-2-1
Poles Description:
3P
Coil Technology:
built-in bidirectional peak limiting diode suppressor
Product Name:
TeSys Deca
Rated Breaking Capacity:
1100 A at 440 V for power circuit conforming to IEC 60947
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Electrical Durability:
0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
Mechanical Durability:
8000000 cycles
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 1260 A at 440 V for power circuit conforming to IEC 60947
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Protective Treatment:
TH IEC 60068-2-30
[Icw] Rated Short-Time Withstand Current:
250 A 40°C - 10 min for power circuit || 550 A 40°C - 1 min for power circuit || 950 A 40°C - 10 s for power circuit || 1100 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms
Contactor Application:
resistive load || motor control
Motor Power Kw:
30 kW at 220...230 V AC 50-60 Hz || 55 kW at 380...400 V AC 50-60 Hz || 59 kW at 415 V AC 50-60 Hz || 59 kW at 440 V AC 50-60 Hz || 75 kW at 500 V AC 50-60 Hz || 80 kW at 660...690 V AC 50-60 Hz || 65 kW at 1000 V AC 50-60 Hz
Protective Cover:
with
Average Impedance:
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Product Certifications:
BV || CCC || CSA || DNV || GL || RINA || UL || EAC || UKCA
Auxiliary Contact Composition:
1 NO + 1 NC
Ambient Air Temperature For Storage:
-60-80°C
Country of Origin:
France
Mounting Support:
plate || rail
Range:
TeSys
Insulation Resistance:
> 10 MOhm for Signaling circuit
Pollution Degree:
3
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
Interlocking Type:
mechanical || electrical
Overvoltage Category:
III
Warranty:
18 months
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 250 A gG at <= 690 V coordination type 1 for power circuit || 200 A gG at <= 690 V coordination type 2 for power circuit
Pole Contact Composition:
3 NO
[Ith] Conventional Free Air Thermal Current:
200 A (at 60°C) for power circuit
Device Presentation:
preassembled with reversing power busbar
[Ie] Rated Operational Current:
200 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 115 A (at <60°C) at <= 440 V AC AC-3 for power circuit
Weight:
6.35 kg
Minimum Switching Voltage:
17 V for Signaling circuit
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Control Circuit Voltage Limits:
0.3...0.5 Uc 55-55°C drop-out AC 50/60 Hz || 0.8...1.15 Uc 55-55°C operational AC 50/60 Hz
Net Weight:
6.35 kg
Mercury Free:
Yes
Ip Degree Of Protection:
IP20 front face IEC 60529
Operating Altitude:
0...9842.52 ft (0...3000 m)