Schneider Electric

Schneider Electric LC2D12BDV TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V DC coil

(No reviews yet) Write a Review
SKU:
LC2D12BDV
MPN:
LC2D12BDV
Condition:
New
Fire Resistance:
850°C IEC 60695-2-1
Net Weight:
1.027 kg
Insulation Resistance:
> 10 MOhm for Signaling circuit
Mechanical Durability:
30 Mcycles
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Time Constant:
28 ms
Device Short Name:
LC2D
Weight:
1.027 kg
Poles Description:
3P
Device Presentation:
preassembled with reversing power busbar
Eu Rohs Directive:
Compliant with Exemptions
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Country of Origin:
France
Maximum Operating Rate:
3600 cyc/h 60°C
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
Irms Rated Making Capacity:
250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
Climatic Withstand:
IACS E10 || IEC 60947-1 Annex Q category D
Inrush Power In W:
5.4-5.4 W 20°C)
Pvc Free:
Yes
Utilisation Category:
AC-3 || AC-1
Overvoltage Category:
III
Minimum Switching Current:
5 mA for Signaling circuit
Auxiliary Contact Composition:
1 NO + 1 NC
Product Certifications:
DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
Average Impedance:
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
Width:
90 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
[Icw] Rated Short-Time Withstand Current:
30 A 40°C - 10 min for power circuit || 61 A 40°C - 1 min for power circuit || 105 A 40°C - 10 s for power circuit || 210 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Range:
TeSys || TeSys Deca
Electrical Durability:
2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V
Pollution Degree:
3
Maximum Horse Power Rating:
1 hp at 115 V AC 60 Hz for 1 phase motors || 2 hp at 230/240 V AC 60 Hz for 1 phase motors || 3 hp at 200/208 V AC 60 Hz for 3 phase motors || 3 hp at 230/240 V AC 60 Hz for 3 phase motors || 7.5 hp at 460/480 V AC 60 Hz for 3 phase motors || 10 hp a
Signaling Circuit Frequency:
25...400 Hz
Control Circuit Type:
DC standard
Power Dissipation Per Pole:
1.56 W AC-1 || 0.36 W AC-3
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
Protective Cover:
with
Contactor Application:
motor control || resistive load
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Motor Power Kw:
3 kW at 220...230 V AC 50 Hz || 5.5 kW at 380...400 V AC 50 Hz || 5.5 kW at 415...440 V AC 50 Hz || 7.5 kW at 500 V AC 50 Hz || 7.5 kW at 660...690 V AC 50 Hz
Minimum Switching Voltage:
17 V for Signaling circuit
$385.00

Description

TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 12A/690V AC-3 (5.5kW@400V). It provides 24V DC coils with transient suppressor module, 2NO+2NC built-in auxiliary contacts (NC mirror contacts), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical and electrical interlock. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
View AllClose