Schneider Electric LC2D12F7 TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 110 V AC coil
Schneider Electric
$364.20
LC2D12F7 is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications. Rated 12A AC-3 5.5kW@400V, it includes a 110V 50/60Hz AC coil, 2NO+2NC aux contacts, a mechanical interlock. LC2D12F7 is a 3-pole TeSys D reversing contactor from Schneider Electric for motor applications up to 5.5kW@400V. It includes a 110V 50/60Hz AC coil and 2NO+2NC built-in auxiliary contacts, NC mirror certified. Compact, DIN-rail mounting, with mechanical interlock and pre-wired reversing circuit, it procures reliability and durability. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant (RoHs/Reach). Compact product, 90mm wide, for DIN-rail and panel mounting. Assembled with mechanical interlock and pre-wired reversing circuit. Clear separation between power and control circuits, easy front access to coil and auxiliary contacts connections. Equipped with a 110V AC coil that can be supplied at 50Hz or 60Hz. Provides 4 built-in auxiliary contacts 2NO + 2NC, NC contacts are mirror certified suitable to be included in the control of safety systems. High electrical durability, guaranteed for 2 million cycles at 12A AC-3 440V, for demanding motor switching applications. Robust design with high making and breaking capacities up to 20 In. Connection by screw clamp terminals.
- Ambient Air Temperature For Storage:
- -60-80°C
- Mechanical Durability:
- 15 Mcycles
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Motor Power Kw:
- 3 kW at 220...230 V AC 50 Hz || 5.5 kW at 380...400 V AC 50 Hz || 5.5 kW at 415 V AC 50 Hz || 5.5 kW at 440 V AC 50 Hz || 7.5 kW at 500 V AC 50 Hz || 7.5 kW at 660...690 V AC 50 Hz
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Rated Breaking Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity:
- 250 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Power Dissipation Per Pole:
- 1.56 W AC-1 || 0.36 W AC-3 || 0.36 W AC-3e
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Heat Dissipation:
- 2-3 W 50/60 Hz
- [Uc] Control Circuit Voltage:
- 110 V AC 50/60 Hz
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Contactor Application:
- resistive load || motor control
- Fire Resistance:
- 850°C IEC 60695-2-1
- Depth:
- 86 mm
- Utilisation Category:
- AC-3 || AC-1 || AC-3e
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 25 A (at 60°C) for power circuit
- Pollution Degree:
- 3
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 40 A gG at <= 690 V coordination type 1 for power circuit || 25 A gG at <= 690 V coordination type 2 for power circuit
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Tightening Torque:
- power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
- Protective Cover:
- with
- Protective Treatment:
- TH IEC 60068-2-30
- Toxic Heavy Metal Free:
- Yes
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Connections - Terminals:
- power circuit screw clamp terminals 1 1-4 mm²flexible without cable end || power circuit screw clamp terminals 2 1-4 mm²flexible without cable end || power circuit screw clamp terminals 1 1-4 mm²flexible with cable end || power circuit screw clamp
- Country of Origin:
- Indonesia
- Mercury Free:
- Yes
- Device Short Name:
- LC2D
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Warranty:
- 18 months
- Rohs Exemption Information:
- Yes
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Average Impedance:
- 2.5 mOhm - Ith 25 A 50 Hz for power circuit
- Range:
- TeSys || TeSys Deca
- [Ie] Rated Operational Current:
- 25 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 12 A (at <60°C) at <= 440 V AC AC-3e for power circuit
- Pole Contact Composition:
- 3 NO
- Sustainable Offer Status:
- Green Premium product
- Circularity Profile:
- ENVEOLI1501004
- Mounting Support:
- rail || plate
- Product Or Component Type:
- reversing contactor
- Signaling Circuit Frequency:
- 25...400 Hz
- Weight:
- 0.697 kg