- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Pvc Free:
- Yes
- Range:
- TeSys || TeSys Deca
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 32 A (at 60°C) for power circuit
- Pole Contact Composition:
- 3 NO
- Rohs Exemption Information:
- Yes
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Depth:
- 86 mm
- Signaling Circuit Frequency:
- 25...400 Hz
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Flame Retardance:
- V1 conforming to UL 94
- Power Dissipation Per Pole:
- 0.8 W AC-3 || 2.5 W AC-1 || 0.8 W AC-3e
- Overvoltage Category:
- III
- Contactor Application:
- motor control || resistive load
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Product Certifications:
- DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
- Product Name:
- TeSys D || TeSys Deca
- Protective Cover:
- with
- Control Circuit Type:
- AC 50/60 Hz
- Mechanical Durability:
- 15 Mcycles
- Product Or Component Type:
- reversing contactor
- [Uc] Control Circuit Voltage:
- 48 V AC 50/60 Hz
- Protective Treatment:
- TH IEC 60068-2-30
- Toxic Heavy Metal Free:
- Yes
- Electrical Durability:
- 1.65 Mcycles 18 A AC-3 <= 440 V || 1 Mcycles 32 A AC-1 <= 440 V || 1.65 Mcycles 18 A AC-3e <= 440 V
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Motor Power Kw:
- 4 kW at 220...230 V AC 50-60 Hz || 7.5 kW at 380...400 V AC 50-60 Hz || 9 kW at 415 V AC 50-60 Hz || 9 kW at 440 V AC 50-60 Hz || 10 kW at 500 V AC 50-60 Hz || 10 kW at 660...690 V AC 50-60 Hz
- Weight:
- 0.707 kg
- Connections - Terminals:
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Net Weight:
- 0.707 kg
- Rated Breaking Capacity:
- 300 A at 440 V for power circuit conforming to IEC 60947
- Fire Resistance:
- 850°C IEC 60695-2-1
- Utilisation Category:
- AC-3 || AC-1 || AC-3e
- Mercury Free:
- Yes
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 300 A at 440 V for power circuit conforming to IEC 60947
- Maximum Horse Power Rating:
- 1 hp at 115 V AC 60 Hz for 1 phase motors || 3 hp at 230/240 V AC 60 Hz for 1 phase motors || 5 hp at 200/208 V AC 60 Hz for 3 phase motors || 5 hp at 230/240 V AC 60 Hz for 3 phase motors || 10 hp at 460/480 V AC 60 Hz for 3 phase motors || 15 hp at
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Interlocking Type:
- mechanical
- [Icw] Rated Short-Time Withstand Current:
- 40 A 40°C - 10 min for power circuit || 84 A 40°C - 1 min for power circuit || 145 A 40°C - 10 s for power circuit || 240 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms fo
- Device Presentation:
- preassembled with reversing power busbar