Schneider Electric

Schneider Electric LC2D18G7 TeSys Deca IEC contactor, 18 A, 3 P, 10 HP at 480 VAC, reversing, 120 VAC 50/60 Hz coil

(No reviews yet) Write a Review
SKU:
LC2D18G7
MPN:
LC2D18G7
Condition:
New
Device Short Name:
LC2D
Range:
TeSys || TeSys Deca
Minimum Switching Current:
5 mA for Signaling circuit
Signaling Circuit Frequency:
25...400 Hz
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Connections - Terminals:
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
Pvc Free:
Yes
Ip Degree Of Protection:
IP20 front face IEC 60529
Coil Technology:
without built-in suppressor module
Mounting Support:
plate || rail
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Device Presentation:
preassembled with reversing power busbar
Warranty:
18 months
Operating Time:
12...22 ms closing || 4...19 ms opening
Toxic Heavy Metal Free:
Yes
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Environmental Disclosure:
ENVPEP1501004
Climatic Withstand:
IACS E10 || IEC 60947-1 Annex Q category D
Maximum Horse Power Rating:
1 hp at 115 V AC 60 Hz for 1 phase motors || 3 hp at 230/240 V AC 60 Hz for 1 phase motors || 5 hp at 200/208 V AC 60 Hz for 3 phase motors || 5 hp at 230/240 V AC 60 Hz for 3 phase motors || 10 hp at 460/480 V AC 60 Hz for 3 phase motors || 15 hp at
Sustainable Offer Status:
Green Premium product
Protective Treatment:
TH IEC 60068-2-30
Weight:
0.707 kg
Depth:
86 mm
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Utilisation Category:
AC-3 || AC-1
Overvoltage Category:
III
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 50 A gG at <= 690 V coordination type 1 for power circuit || 35 A gG at <= 690 V coordination type 2 for power circuit
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Electrical Durability:
1.65 Mcycles 18 A AC-3 <= 440 V || 1 Mcycles 32 A AC-1 <= 440 V
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Operating Altitude:
0...9842.52 ft (0...3000 m)
Rated Breaking Capacity:
300 A at 440 V for power circuit conforming to IEC 60947
Circularity Profile:
ENVEOLI1501004
Interlocking Type:
mechanical
Contactor Application:
resistive load || motor control
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
[Ie] Rated Operational Current:
18 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 32 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Average Impedance:
2.5 mOhm - Ith 32 A 50 Hz for power circuit
Ambient Air Temperature For Storage:
-60-80°C
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Country of Origin:
Indonesia
Poles Description:
3P
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Tightening Torque:
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || contro
$416.16

Description

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for any type of application. They can be used to create motor starters for almost any type of application. TeSys D contactors offer quick simple setup, while maintaining a compact size. Contactors have both Horsepower and Kw motor rating for international acceptance. An extennsive line of accessories makes it easy to meet the requirements of most applications. These contactors have UL, CSA, GOST, RINA, BV, CCC, DNV, GL, LROS certifications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).