Schneider Electric

Schneider Electric LC2D25B7V TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 24 V AC coil

(No reviews yet) Write a Review
SKU:
LC2D25B7V
MPN:
LC2D25B7V
Condition:
New
Device Presentation:
preassembled with reversing power busbar
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
Contactor Application:
motor control || resistive load
Depth:
92 mm
Control Circuit Type:
AC 50/60 Hz
Warranty:
18 months
Sustainable Offer Status:
Green Premium product
Coil Technology:
without built-in suppressor module
Signaling Circuit Frequency:
25...400 Hz
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Power Dissipation Per Pole:
1.25 W AC-3 || 3.2 W AC-1
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Net Weight:
0.787 kg
Utilisation Category:
AC-1 || AC-3
Minimum Switching Current:
5 mA for Signaling circuit
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Product Name:
TeSys Deca
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Country of Origin:
France
Ambient Air Temperature For Operation:
-40-60°C || 60-70°C with derating
Auxiliary Contacts Type:
mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
Auxiliary Contact Composition:
1 NO + 1 NC
Device Short Name:
LC2D
Rohs Exemption Information:
Yes
Operating Altitude:
0...9842.52 ft (0...3000 m)
Eu Rohs Directive:
Compliant
Product Or Component Type:
reversing contactor
Maximum Horse Power Rating:
3 hp at 230/240 V AC 60 Hz for 1 phase motors || 5 hp at 200/208 V AC 60 Hz for 3 phase motors || 2 hp at 115 V AC 60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 60 Hz for 3 phase motors || 15 hp at 460/480 V AC 60 Hz for 3 phase motors || 20 hp
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
Control Circuit Voltage Limits:
0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
Minimum Switching Voltage:
17 V for Signaling circuit
[Ie] Rated Operational Current:
25 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
Operating Time:
12...22 ms closing || 4...19 ms opening
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Rated Breaking Capacity:
450 A at 440 V for power circuit conforming to IEC 60947
Ambient Air Temperature For Storage:
-60-80°C
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
China Rohs Regulation:
Pro-active China RoHS declaration (out of China RoHS legal scope)
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
Product Certifications:
DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
Ip Degree Of Protection:
IP20 front face IEC 60529
[Uc] Control Circuit Voltage:
24 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
[Icw] Rated Short-Time Withstand Current:
50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
Pvc Free:
Yes
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Overvoltage Category:
III
Fire Resistance:
850°C IEC 60695-2-1
$468.12

Description

TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 25A/690V AC-3 (11kW@400V). It provides 24V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
View AllClose