- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Control Circuit Voltage Limits:
- <= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC || 0.8...1.1 Uc -40-60°C operational DC || 1...1.1 Uc 60-70°C operational AC/DC
- Sustainable Offer Status:
- Green Premium product
- Rated Breaking Capacity:
- 450 A at 440 V for power circuit conforming to IEC 60947
- [Ie] Rated Operational Current:
- 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit || 25 A (at <60°C) at <= 440 V AC AC-3 for power circuit
- Weight:
- 0.913 kg
- Average Impedance:
- 2 mOhm - Ith 40 A 50 Hz for power circuit
- Maximum Horse Power Rating:
- 2 hp at 115 V AC 60 Hz for 1 phase motors || 3 hp at 230/240 V AC 60 Hz for 1 phase motors || 7.5 hp at 200/208 V AC 60 Hz for 3 phase motors || 7.5 hp at 230/240 V AC 60 Hz for 3 phase motors || 15 hp at 460/480 V AC 60 Hz for 3 phase motors || 20 h
- Warranty:
- 18 months
- Fire Resistance:
- 850°C IEC 60695-2-1
- Motor Power Kw:
- 5.5 kW at 220...230 V AC 50 Hz || 11 kW at 380...400 V AC 50 Hz || 11 kW at 415 V AC 50 Hz || 11 kW at 440 V AC 50 Hz || 15 kW at 500 V AC 50 Hz || 15 kW at 660...690 V AC 50 Hz
- Mercury Free:
- Yes
- Connections - Terminals:
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
- Interlocking Type:
- mechanical
- Rohs Exemption Information:
- Yes
- Hold-In Power Consumption In W:
- 0.6-0.6 W 20°C
- Environmental Disclosure:
- ENVPEP1609001EN
- Inrush Power In W:
- 14-14 W 20°C
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
- Height:
- 85 mm
- Width:
- 90 mm
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Operating Time:
- 45...55 ms closing || 20...90 ms opening
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Product Name:
- Tesys Deca green || TeSys Deca
- Standards:
- EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
- Contactor Application:
- motor control || resistive load
- [Icw] Rated Short-Time Withstand Current:
- 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Electrical Durability:
- 2 Mcycles 21 A AC-3 <= 440 V || 0.9 Mcycles 40 A AC-1 <= 440 V
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || power
- Minimum Switching Current:
- 5 mA for Signaling circuit
- [Uc] Control Circuit Voltage:
- 24...60 V AC 50/60 Hz || 24...60 V DC
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Mechanical Durability:
- 15 Mcycles
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Utilisation Category:
- AC-1 || AC-3
- Coil Technology:
- built-in bidirectional peak limiting
- Product Or Component Type:
- reversing contactor
- Mounting Support:
- rail || plate
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Depth:
- 92 mm
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ambient Air Temperature For Storage:
- -60-80°C
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
- Circularity Profile:
- ENVEOLI1609001EN
- Color:
- Gray SE GREY 6) || Green SE GREEN 2)
- Pole Contact Composition:
- 3 NO
- Signaling Circuit Frequency:
- 25...400 Hz