Schneider Electric LC2D25D7 TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 42 V AC coil
Schneider Electric
$462.12
TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 25A/690V AC-3 (11kW@400V). It provides 42V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
- Environmental Disclosure:
- ENVPEP110229EN
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Poles Description:
- 3P
- Product Name:
- TeSys Deca
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Electrical Durability:
- 1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
- [Uc] Control Circuit Voltage:
- 42 V AC 50/60 Hz
- Interlocking Type:
- mechanical
- Average Impedance:
- 2 mOhm - Ith 40 A 50 Hz for power circuit
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
- Connections - Terminals:
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Circularity Profile:
- ENVEOLI110229EN
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Fire Resistance:
- 850°C IEC 60695-2-1
- Protective Cover:
- with
- Contactor Application:
- motor control || resistive load
- Product Certifications:
- DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA
- Protective Treatment:
- TH IEC 60068-2-30
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Utilisation Category:
- AC-1 || AC-3 || AC-3e
- [Ie] Rated Operational Current:
- 25 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Ambient Air Temperature For Storage:
- -60-80°C
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Hold-In Power Consumption In Va:
- 7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
- Warranty:
- 18 months
- Coil Technology:
- without built-in suppressor module
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
- Pvc Free:
- Yes
- Pollution Degree:
- 3
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Rohs Exemption Information:
- Yes
- Signaling Circuit Frequency:
- 25...400 Hz
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Maximum Horse Power Rating:
- 3 hp at 230/240 V AC 60 Hz for 1 phase motors || 5 hp at 200/208 V AC 60 Hz for 3 phase motors || 2 hp at 115 V AC 60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 60 Hz for 3 phase motors || 15 hp at 460/480 V AC 60 Hz for 3 phase motors || 20 hp
- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- Control Circuit Type:
- AC 50/60 Hz
- Insulation Resistance:
- > 10 MOhm for Signaling circuit