- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Mounting Support:
- rail || plate
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Rohs Exemption Information:
- Yes
- Control Circuit Type:
- AC 50/60 Hz
- Motor Power Kw:
- 5.5 kW at 220...230 V AC 50-60 Hz || 11 kW at 380...400 V AC 50-60 Hz || 11 kW at 415 V AC 50-60 Hz || 11 kW at 440 V AC 50-60 Hz || 15 kW at 500 V AC 50-60 Hz || 15 kW at 660...690 V AC 50-60 Hz
- Average Impedance:
- 2 mOhm - Ith 40 A 50 Hz for power circuit
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
- Power Dissipation Per Pole:
- 1.25 W AC-3 || 3.2 W AC-1 || 1.25 W AC-3e
- Pole Contact Composition:
- 3 NO
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Environmental Disclosure:
- ENVPEP110229EN
- Product Or Component Type:
- reversing contactor
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Electrical Durability:
- 1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Heat Dissipation:
- 2-3 W 50/60 Hz
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Country of Origin:
- United States
- Range:
- TeSys || TeSys Deca
- Rated Breaking Capacity:
- 450 A at 440 V for power circuit conforming to IEC 60947
- Overvoltage Category:
- III
- Protective Treatment:
- TH IEC 60068-2-30
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Warranty:
- 18 months
- Poles Description:
- 3P
- Sustainable Offer Status:
- Green Premium product
- Product Certifications:
- DNV || CSA || CCC || UL || GL || LROS (Lloyds register of shipping) || BV || RINA || GOST || UKCA || CB
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Icw] Rated Short-Time Withstand Current:
- 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Fire Resistance:
- 850°C IEC 60695-2-1
- Product Name:
- TeSys D || TeSys Deca
- Protective Cover:
- with
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Ambient Air Temperature For Storage:
- -60-80°C
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Utilisation Category:
- AC-1 || AC-3 || AC-3e
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Minimum Switching Current:
- 5 mA for Signaling circuit