- Control Circuit Voltage Limits:
- 0.3...0.6 Uc -40-70°C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60°C operational AC 50 Hz || 0.85...1.1 Uc -40-60°C operational AC 60 Hz || 1...1.1 Uc 60-70°C operational AC 50/60 Hz
- [Icw] Rated Short-Time Withstand Current:
- 50 A 40°C - 10 min for power circuit || 120 A 40°C - 1 min for power circuit || 240 A 40°C - 10 s for power circuit || 380 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- Device Short Name:
- LC2D
- Environmental Disclosure:
- ENVPEP110229EN
- Operating Time:
- 12...22 ms closing || 4...19 ms opening
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- Power Dissipation Per Pole:
- 1.25 W AC-3 || 3.2 W AC-1 || 1.25 W AC-3e
- Eu Rohs Directive:
- Compliant
- Pole Contact Composition:
- 3 NO
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Depth:
- 92 mm
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Product Name:
- TeSys D || TeSys Deca
- [Ie] Rated Operational Current:
- 25 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC AC-1 for power circuit
- Maximum Horse Power Rating:
- 3 hp at 230/240 V AC 60 Hz for 1 phase motors || 5 hp at 200/208 V AC 60 Hz for 3 phase motors || 2 hp at 115 V AC 60 Hz for 1 phase motors || 7.5 hp at 230/240 V AC 60 Hz for 3 phase motors || 15 hp at 460/480 V AC 60 Hz for 3 phase motors || 20 hp
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Fire Resistance:
- 850°C IEC 60695-2-1
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 40 A gG at <= 690 V coordination type 2 for power circuit
- Coil Technology:
- without built-in suppressor module
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Average Impedance:
- 2 mOhm - Ith 40 A 50 Hz for power circuit
- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Weight:
- 0.787 kg
- Country of Origin:
- Indonesia
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 450 A at 440 V for power circuit conforming to IEC 60947
- Auxiliary Contact Composition:
- 1 NO + 1 NC
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Minimum Switching Current:
- 5 mA for Signaling circuit
- Signaling Circuit Frequency:
- 25...400 Hz
- Poles Description:
- 3P
- Warranty:
- 18 months
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 40 A (at 60°C) for power circuit
- Electrical Durability:
- 1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V || 1.65 Mcycles 25 A AC-3e <= 440 V
- Device Presentation:
- preassembled with reversing power busbar
- Net Weight:
- 0.787 kg
- Flame Retardance:
- V1 conforming to UL 94
- Contactor Application:
- motor control || resistive load
- [Ui] Rated Insulation Voltage:
- power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
- Heat Dissipation:
- 2-3 W 50/60 Hz
- Height:
- 85 mm
- Protective Cover:
- with
- Circularity Profile:
- ENVEOLI110229EN
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Rated Breaking Capacity:
- 450 A at 440 V for power circuit conforming to IEC 60947
- Rohs Exemption Information:
- Yes