- Maximum Operating Rate:
- 3600 cyc/h 60°C
- Pvc Free:
- Yes
- Poles Description:
- 3P
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
- Ambient Air Temperature For Storage:
- -60-80°C
- Protective Treatment:
- TH IEC 60068-2-30
- Width:
- 90 mm
- Heat Dissipation:
- 2-3 W 50/60 Hz
- Signaling Circuit Frequency:
- 25...400 Hz
- Weight:
- 0.797 kg
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
- Product Certifications:
- UL || CSA || RINA || GOST || CCC || DNV || LROS (Lloyds register of shipping) || GL || BV || UKCA
- Product Name:
- TeSys D || TeSys Deca
- Range:
- TeSys || TeSys Deca
- Device Short Name:
- LC2D
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
- Utilisation Category:
- AC-1 || AC-3 || AC-3e
- Control Circuit Type:
- AC 50/60 Hz
- Connections - Terminals:
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
- Auxiliary Contacts Type:
- mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Average Impedance:
- 2 mOhm - Ith 50 A 50 Hz for power circuit
- Product Or Component Type:
- reversing contactor
- Fire Resistance:
- 850°C IEC 60695-2-1
- Net Weight:
- 0.797 kg
- Rohs Exemption Information:
- Yes
- Interlocking Type:
- mechanical
- Inrush Power In Va:
- 70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
- Standards:
- CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
- Contactor Application:
- resistive load || motor control
- Pole Contact Composition:
- 3 NO
- Sustainable Offer Status:
- Green Premium product
- Eu Rohs Directive:
- Compliant
- Operating Altitude:
- 0...9842.52 ft (0...3000 m)
- [Uc] Control Circuit Voltage:
- 115 V AC 50/60 Hz
- Mechanical Durability:
- 15 Mcycles
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mounting Support:
- plate || rail
- Flame Retardance:
- V1 conforming to UL 94
- Circularity Profile:
- ENVEOLI110229EN
- [Ue] Rated Operational Voltage:
- power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
- Motor Power Kw:
- 7.5 kW at 220...230 V AC 50-60 Hz || 15 kW at 380...400 V AC 50-60 Hz || 15 kW at 415 V AC 50-60 Hz || 15 kW at 440 V AC 50-60 Hz || 18.5 kW at 500 V AC 50-60 Hz || 18.5 kW at 660...690 V AC 50-60 Hz
- Depth:
- 92 mm
- Warranty:
- 18 months
- Minimum Switching Voltage:
- 17 V for Signaling circuit
- [Icw] Rated Short-Time Withstand Current:
- 60 A 40°C - 10 min for power circuit || 138 A 40°C - 1 min for power circuit || 260 A 40°C - 10 s for power circuit || 430 A 40°C - 1 s for power circuit || 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms f
- China Rohs Regulation: