Schneider Electric

Schneider Electric LC2D32G7V TeSys Deca reversing contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 120 V AC coil

(No reviews yet) Write a Review
SKU:
LC2D32G7V
MPN:
LC2D32G7V
Condition:
New
Irms Rated Making Capacity:
140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 550 A at 440 V for power circuit conforming to IEC 60947
Weight:
0.797 kg
Rohs Exemption Information:
Yes
Safety Reliability Level:
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Average Impedance:
2 mOhm - Ith 50 A 50 Hz for power circuit
Pollution Degree:
3
Operating Altitude:
0...9842.52 ft (0...3000 m)
[Ie] Rated Operational Current:
32 A (at <60°C) at <= 440 V AC AC-3 for power circuit || 50 A (at <60°C) at <= 440 V AC AC-1 for power circuit
[Uc] Control Circuit Voltage:
120 V AC 50/60 Hz
Insulation Resistance:
> 10 MOhm for Signaling circuit
Standards:
CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
Eu Rohs Directive:
Compliant
Warranty:
18 months
Inrush Power In Va:
70-70 VA 60 Hz cos phi 0.75 (at 20°C) || 70-70 VA 50 Hz cos phi 0.75 (at 20°C)
Fire Resistance:
850°C IEC 60695-2-1
Rated Breaking Capacity:
550 A at 440 V for power circuit conforming to IEC 60947
[Ith] Conventional Free Air Thermal Current:
10 A (at 60°C) for Signaling circuit || 50 A (at 60°C) for power circuit
Climatic Withstand:
IACS E10 || IEC 60947-1 Annex Q category D
[Ue] Rated Operational Voltage:
power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
Product Or Component Type:
reversing contactor
Associated Fuse Rating:
10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 63 A gG at <= 690 V coordination type 1 for power circuit || 63 A gG at <= 690 V coordination type 2 for power circuit
Minimum Switching Voltage:
17 V for Signaling circuit
Coil Technology:
without built-in suppressor module
Auxiliary Contact Composition:
1 NO + 1 NC
Product Name:
TeSys Deca
Control Circuit Type:
AC 50/60 Hz
Utilisation Category:
AC-3 || AC-1
Non-Overlap Time:
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Mounting Support:
plate || rail
Maximum Horse Power Rating:
2 hp at 115 V AC 60 Hz for 1 phase motors || 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 7.5 hp at 200/208 V AC 60 Hz for 3 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 20 hp at 460/480 V AC 60 Hz for 3 phase motors || 30 hp
Tightening Torque:
control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || contro
Device Short Name:
LC2D
Poles Description:
3P
Depth:
92 mm
Circularity Profile:
ENVEOLI110229EN
Power Dissipation Per Pole:
2 W AC-3 || 5 W AC-1
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947
Connections - Terminals:
control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
Electrical Durability:
1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V
Signaling Circuit Frequency:
25...400 Hz
Hold-In Power Consumption In Va:
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20°C) || 7-7 VA 50 Hz cos phi 0.3 (at 20°C)
Protective Cover:
with
Minimum Switching Current:
5 mA for Signaling circuit
[Ui] Rated Insulation Voltage:
power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || Signaling circuit 690 V IEC 60947-1 || Signaling circuit 600 V CSA || Signaling circuit 600 V UL
Mechanical Durability:
15 Mcycles
Ambient Air Temperature For Storage:
-60-80°C
Interlocking Type:
electrical and mechanical
Height:
85 mm
Mechanical Robustness:
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
Overvoltage Category:
III
$680.34

Description

TeSys D reversing contactor, 3 poles (3NO), for motor control applications up to 32A/690V AC-3 (15kW@400V). It provides 120V 50/60Hz AC coils, 2NO+2NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (90mm width), DIN-rail mounting or screw fixing. With pre-wired reversing power connections, mechanical interlock (without electrical interlocking). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
View AllClose