- Control Circuit Voltage Limits:
- <= 0.1 Uc -40-70°C drop-out AC/DC || 0.85...1.1 Uc -40-60°C operational AC || 0.8...1.1 Uc -40-60°C operational DC || 1...1.1 Uc 60-70°C operational AC/DC
- Mercury Free:
- Yes
- Interlocking Type:
- mechanical
- Product Or Component Type:
- reversing contactor
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Hold-In Power Consumption In Va:
- 1-1 VA 20°C) 50/60 Hz
- Motor Power Kw:
- 11 kW at 220...230 V AC 50 Hz || 18.5 kW at 380...400 V AC 50 Hz || 22 kW at 415 V AC 50 Hz || 22 kW at 440 V AC 50 Hz || 22 kW at 500 V AC 50 Hz || 30 kW at 660...690 V AC 50 Hz
- Connections - Terminals:
- control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit scr
- Overvoltage Category:
- III
- Insulation Resistance:
- > 10 MOhm for Signaling circuit
- Ambient Air Temperature For Operation:
- -40-60°C || 60-70°C with derating
- Mechanical Robustness:
- vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
- Flame Retardance:
- V1 conforming to UL 94
- Range:
- TeSys || TeSys Deca
- Power Dissipation Per Pole:
- 2.4 W AC-3 || 5.4 W AC-1 || 2.4 W AC-3e
- Ambient Air Temperature For Storage:
- -60-80°C
- Inrush Power In W:
- 16-16 W 20°C
- Device Presentation:
- preassembled with reversing power busbar
- Maximum Horse Power Rating:
- 3 hp at 115 V AC 60 Hz for 1 phase motors || 5 hp at 230/240 V AC 60 Hz for 1 phase motors || 10 hp at 200/208 V AC 60 Hz for 3 phase motors || 10 hp at 230/240 V AC 60 Hz for 3 phase motors || 30 hp at 460/480 V AC 60 Hz for 3 phase motors || 30 hp
- Irms Rated Making Capacity:
- 140 A AC for Signaling circuit conforming to IEC 60947-5-1 || 250 A DC for Signaling circuit conforming to IEC 60947-5-1 || 800 A at 440 V for power circuit conforming to IEC 60947
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947
- Tightening Torque:
- control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connecto
- Non-Overlap Time:
- 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Device Short Name:
- LC2D
- Warranty:
- 18 months
- [Icw] Rated Short-Time Withstand Current:
- 100 A - 1 s for Signaling circuit || 120 A - 500 ms for Signaling circuit || 140 A - 100 ms for Signaling circuit || 320 A 40°C - 10 s for power circuit || 720 A 40°C - 1 s for power circuit || 72 A 40°C - 10 min for power circuit || 165 A 40°C - 1 m
- Product Certifications:
- CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 60°C) for Signaling circuit || 60 A (at 60°C) for power circuit
- Climatic Withstand:
- IACS E10 || IEC 60947-1 Annex Q category D
- Circularity Profile:
- ENVEOLI1607010EN
- Protective Treatment:
- TH IEC 60068-2-30
- Rated Breaking Capacity:
- 800 A at 440 V for power circuit conforming to IEC 60947
- Mounting Support:
- rail || plate
- Ip Degree Of Protection:
- IP20 front face IEC 60529
- [Ie] Rated Operational Current:
- 60 A (at <60°C) at <= 440 V AC-1 for power circuit || 40 A (at <60°C) at <= 440 V AC-3 for power circuit || 40 A (at <60°C) at <= 440 V AC-3e for power circuit
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Rohs Exemption Information:
- Yes
- Utilisation Category:
- AC-3 || AC-1 || AC-3e
- Pole Contact Composition:
- 3 NO
- Color:
- Gray SE GREY 6) || Green SE GREEN 2)
- Hold-In Power Consumption In W:
- 0.7-0.7 W 20°C
- Fire Resistance:
- 850°C IEC 60695-2-1
- Control Circuit Type:
- AC 50/60 Hz AC/DC electronic || DC AC/DC electronic
- Associated Fuse Rating:
- 10 A gG for Signaling circuit conforming to IEC 60947-5-1 || 80 A gG at <= 690 V coordination type 1 for power circuit || 80 A gG at <= 690 V coordination type 2 for power circuit
- Height:
- 122 mm
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Inrush Power In Va:
- 15-15 VA 50/60 Hz 20°C)
- Country of Origin:
- France